Table 2-3 – Design Day Data for California Cities
City |
Latitude |
Elevation (ft) |
Longitude |
Cooling |
|
Heating | ||||||||||||
0.10% |
0.50% |
1.00% |
2.00% |
Design Wetbulb 0.1% |
Design Wetbulb 0.5% |
Outdoor Daily Range |
Winter Median of Extremes |
Design Drybulb (0.2%) |
Design Drybulb (0.6%) |
HDD* | ||||||||
DB |
MCWB |
DB |
MCWB |
DB |
MCWB |
DB |
MCWB | |||||||||||
Adelanto |
34.6 |
2865 |
117.4 |
105 |
67 |
101 |
65 |
100 |
64 |
97 |
62 |
70 |
68 |
39 |
14 |
24 |
27 |
1654 |
din RS |
41.2 |
4195 |
121 |
96 |
61 |
92 |
60 |
91 |
60 |
88 |
59 |
65 |
63 |
43 |
-7 |
-2 |
4 |
- |
Agoura Hills |
34.2 |
700 |
118.8 |
103 |
70 |
96 |
68 |
94 |
68 |
90 |
66 |
73 |
71 |
29 |
27 |
31 |
34 |
- |
Alameda NAS |
37.8 |
15 |
122.3 |
88 |
65 |
82 |
64 |
80 |
64 |
76 |
62 |
66 |
64 |
21 |
35 |
38 |
40 |
2507 |
Alamo |
37.9 |
410 |
122.9 |
102 |
69 |
97 |
68 |
96 |
68 |
92 |
66 |
72 |
70 |
30 |
23 |
28 |
31 |
- |
Albany |
37.9 |
40 |
122.3 |
88 |
65 |
83 |
64 |
81 |
64 |
77 |
62 |
66 |
64 |
16 |
30 |
35 |
38 |
- |
Alderpoint |
40.2 |
460 |
123.6 |
100 |
69 |
95 |
67 |
94 |
67 |
90 |
65 |
70 |
68 |
39 |
21 |
27 |
30 |
3424 |
Alhambra |
34 |
483 |
118.1 |
100 |
71 |
96 |
70 |
94 |
70 |
90 |
68 |
73 |
71 |
25 |
30 |
35 |
37 |
- |
Aliso Viejo |
33.6 |
50 |
117.7 |
91 |
69 |
83 |
68 |
81 |
68 |
76 |
66 |
71 |
69 |
18 |
30 |
33 |
36 |
- |
Almaden AFS |
37.2 |
3470 |
121.9 |
95 |
62 |
90 |
60 |
89 |
60 |
85 |
59 |
64 |
62 |
20 |
20 |
25 |
29 |
4468 |
Alondra Park |
33.9 |
50 |
118.3 |
91 |
69 |
86 |
68 |
85 |
68 |
81 |
66 |
71 |
69 |
17 |
35 |
40 |
42 |
- |
Alpine |
32.8 |
1735 |
116.8 |
99 |
69 |
95 |
68 |
94 |
68 |
91 |
67 |
72 |
70 |
35 |
27 |
32 |
35 |
- |
Alta Sierra |
35.7 |
6500 |
118.6 |
87 |
62 |
84 |
61 |
83 |
61 |
80 |
59 |
65 |
63 |
32 |
-4 |
1 |
8 |
2428 |
Altadena |
34.2 |
1200 |
118.1 |
99 |
68 |
94 |
67 |
92 |
67 |
88 |
66 |
72 |
70 |
31 |
32 |
37 |
39 |
1920 |
Alturas RS |
41.5 |
4400 |
120.6 |
99 |
62 |
96 |
61 |
95 |
61 |
91 |
59 |
65 |
63 |
43 |
-10 |
-4 |
0 |
6895 |
Alum Rock |
37.4 |
70 |
121.8 |
95 |
68 |
90 |
66 |
88 |
66 |
84 |
64 |
70 |
68 |
22 |
28 |
33 |
36 |
- |
American Canyon |
37.6 |
85 |
122.3 |
93 |
67 |
90 |
66 |
88 |
66 |
84 |
64 |
70 |
68 |
23 |
28 |
33 |
36 |
- |
Anaheim |
33.8 |
158 |
117.9 |
99 |
69 |
92 |
68 |
90 |
68 |
85 |
67 |
73 |
71 |
26 |
32 |
37 |
39 |
- |
Anderson |
40.5 |
430 |
122.3 |
107 |
71 |
103 |
70 |
101 |
70 |
97 |
68 |
72 |
70 |
30 |
26 |
31 |
34 |
- |
Angwin |
38.6 |
1815 |
122.4 |
98 |
66 |
93 |
64 |
92 |
64 |
88 |
62 |
69 |
66 |
33 |
25 |
30 |
33 |
- |
Antioch |
38 |
60 |
121.8 |
102 |
70 |
97 |
68 |
95 |
68 |
91 |
66 |
70 |
69 |
34 |
22 |
28 |
31 |
2627 |
Apple Valley |
34.5 |
2935 |
117.2 |
105 |
66 |
101 |
65 |
100 |
65 |
97 |
64 |
70 |
68 |
38 |
14 |
21 |
25 |
- |
Aptos |
37 |
500 |
121.9 |
94 |
67 |
88 |
66 |
87 |
65 |
83 |
63 |
69 |
67 |
30 |
27 |
32 |
35 |
- |
Arcadia |
34.2 |
475 |
118 |
100 |
69 |
96 |
68 |
95 |
68 |
91 |
67 |
73 |
71 |
30 |
31 |
36 |
38 |
- |
Arcata |
41 |
218 |
124.1 |
75 |
61 |
69 |
59 |
68 |
59 |
65 |
58 |
61 |
60 |
11 |
28 |
31 |
33 |
5029 |
Arden |
38.5 |
80 |
121.4 |
104 |
70 |
100 |
69 |
98 |
69 |
94 |
67 |
73 |
71 |
35 |
28 |
33 |
35 |
- |
Arroyo Grande |
35.1 |
105 |
120.6 |
92 |
66 |
86 |
64 |
84 |
64 |
79 |
62 |
67 |
65 |
18 |
28 |
32 |
35 |
- |
Artesia |
33.8 |
50 |
118.1 |
99 |
71 |
91 |
70 |
89 |
70 |
85 |
68 |
73 |
71 |
23 |
33 |
37 |
40 |
- |
Arvin |
35.2 |
445 |
118.8 |
106 |
71 |
102 |
69 |
101 |
69 |
98 |
68 |
74 |
72 |
30 |
26 |
29 |
32 |
- |
Ash Mtn |
36.5 |
1708 |
118.8 |
105 |
69 |
101 |
68 |
100 |
68 |
97 |
66 |
72 |
70 |
30 |
25 |
31 |
33 |
2703 |
Ashland |
37.7 |
45 |
122.1 |
92 |
66 |
86 |
65 |
85 |
64 |
81 |
62 |
68 |
66 |
24 |
26 |
31 |
34 |
977 |
Atascadero |
35.5 |
837 |
120.7 |
94 |
66 |
89 |
67 |
88 |
67 |
84 |
65 |
70 |
68 |
42 |
25 |
29 |
32 |
- |
Atherton |
37.5 |
50 |
122.2 |
90 |
66 |
84 |
64 |
82 |
64 |
78 |
62 |
68 |
66 |
27 |
23 |
29 |
33 |
- |
Atwater |
37.3 |
150 |
120.6 |
102 |
72 |
99 |
70 |
98 |
69 |
94 |
67 |
74 |
72 |
38 |
24 |
30 |
34 |
- |
Auberry |
37.1 |
2140 |
119.5 |
102 |
69 |
98 |
67 |
97 |
66 |
95 |
64 |
71 |
69 |
36 |
21 |
27 |
30 |
3313 |
Auburn |
38.9 |
1292 |
121.1 |
103 |
69 |
100 |
67 |
99 |
67 |
95 |
66 |
72 |
69 |
33 |
25 |
30 |
33 |
3089 |
Avalon |
33.4 |
25 |
118.3 |
83 |
64 |
75 |
62 |
73 |
62 |
69 |
60 |
68 |
66 |
11 |
37 |
41 |
44 |
2204 |
Avenal |
36 |
550 |
120.1 |
103 |
70 |
98 |
70 |
97 |
70 |
93 |
69 |
73 |
72 |
34 |
23 |
28 |
31 |
- |
Avocado Heights |
34.2 |
550 |
118 |
101 |
69 |
97 |
68 |
95 |
68 |
91 |
68 |
74 |
72 |
30 |
28 |
32 |
35 |
741 |
Azusa |
34.1 |
605 |
118.2 |
101 |
70 |
97 |
69 |
95 |
69 |
91 |
68 |
74 |
72 |
36 |
31 |
36 |
38 |
- |
Baker |
35.3 |
940 |
116.1 |
115 |
73 |
112 |
72 |
111 |
72 |
108 |
70 |
77 |
75 |
29 |
23 |
28 |
31 |
- |
Bakersfield AP |
35.4 |
475 |
119.1 |
106 |
71 |
102 |
70 |
101 |
70 |
98 |
68 |
74 |
72 |
34 |
26 |
31 |
35 |
2185 |
Balch PH |
36.9 |
1720 |
116.0 |
100 |
67 |
97 |
66 |
96 |
66 |
93 |
64 |
71 |
69 |
26 |
26 |
31 |
34 |
- |
Baldwin Park |
34 |
394 |
118 |
100 |
69 |
96 |
69 |
94 |
69 |
90 |
68 |
73 |
72 |
32 |
31 |
36 |
38 |
- |
Banning |
33.9 |
2349 |
116.9 |
104 |
69 |
100 |
68 |
99 |
68 |
96 |
67 |
73 |
71 |
34 |
20 |
26 |
30 |
- |
Barrett Dam |
32.7 |
1623 |
116.7 |
103 |
69 |
97 |
68 |
96 |
68 |
92 |
67 |
73 |
71 |
35 |
22 |
26 |
28 |
2656 |
Barstow |
34.9 |
2162 |
117 |
107 |
69 |
104 |
69 |
103 |
69 |
100 |
67 |
74 |
72 |
35 |
16 |
23 |
27 |
2580 |
Baywood-Los Osos |
35.3 |
100 |
- |
88 |
65 |
82 |
64 |
80 |
64 |
76 |
62 |
67 |
65 |
14 |
31 |
36 |
38 |
- |
Beale AFB |
39.1 |
113 |
121.4 |
105 |
71 |
102 |
70 |
101 |
70 |
97 |
68 |
74 |
72 |
34 |
25 |
28 |
30 |
2835 |
Beaumont |
33.9 |
2605 |
117 |
103 |
68 |
99 |
67 |
98 |
67 |
95 |
66 |
72 |
70 |
38 |
22 |
27 |
30 |
2628 |
Bell |
33.9 |
143 |
118.2 |
97 |
70 |
91 |
69 |
89 |
69 |
85 |
67 |
72 |
70 |
22 |
33 |
38 |
41 |
- |
Bell Gardens |
33.9 |
160 |
118.2 |
97 |
70 |
91 |
69 |
87 |
67 |
85 |
67 |
72 |
70 |
22 |
32 |
37 |
40 |
- |
Bellflower |
33.8 |
73 |
118.1 |
98 |
70 |
91 |
69 |
89 |
69 |
85 |
67 |
72 |
70 |
21 |
32 |
37 |
40 |
- |
Belmont |
37.5 |
33 |
122.3 |
90 |
66 |
84 |
64 |
82 |
64 |
78 |
62 |
68 |
66 |
24 |
29 |
34 |
36 |
- |
Ben Lomond |
37.1 |
450 |
122.1 |
92 |
67 |
85 |
66 |
83 |
65 |
79 |
63 |
69 |
67 |
30 |
25 |
30 |
33 |
- |
Benicia |
38.1 |
55 |
122.1 |
99 |
69 |
93 |
67 |
91 |
67 |
87 |
65 |
70 |
68 |
30 |
28 |
33 |
36 |
|
Berkeley |
37.9 |
345 |
122.3 |
90 |
64 |
83 |
63 |
81 |
63 |
76 |
61 |
66 |
64 |
16 |
33 |
37 |
40 |
2950 |
Berryessa Lake |
38.6 |
480 |
122.1 |
102 |
70 |
98 |
69 |
96 |
69 |
92 |
67 |
72 |
70 |
35 |
26 |
31 |
34 |
- |
Beverly Hills |
34.1 |
268 |
118.2 |
94 |
69 |
88 |
68 |
87 |
68 |
83 |
66 |
71 |
69 |
20 |
39 |
43 |
46 |
- |
Big Bar RS |
40.8 |
1260 |
121.8 |
102 |
68 |
98 |
67 |
97 |
67 |
93 |
65 |
70 |
68 |
46 |
19 |
25 |
28 |
- |
Big Bear Lake |
34.2 |
6745 |
116.9 |
87 |
59 |
83 |
58 |
82 |
58 |
79 |
56 |
64 |
62 |
32 |
-3 |
3 |
7 |
6850 |
Bishop AP |
37.4 |
4108 |
118.4 |
103 |
61 |
100 |
60 |
99 |
60 |
97 |
58 |
65 |
63 |
40 |
5 |
12 |
16 |
4313 |
Blackhawk |
37.7 |
10 |
121.9 |
88 |
65 |
82 |
64 |
80 |
64 |
76 |
62 |
66 |
64 |
21 |
35 |
38 |
40 |
977 |
Blackwells Corner |
35.6 |
644 |
119.9 |
99 |
68 |
94 |
66 |
93 |
66 |
89 |
65 |
71 |
69 |
31 |
23 |
28 |
32 |
- |
Bloomington |
34 |
980 |
117.4 |
106 |
71 |
102 |
70 |
101 |
70 |
98 |
69 |
75 |
73 |
34 |
30 |
35 |
38 |
- |
Blue Canyon AP |
39.3 |
5280 |
120.7 |
88 |
60 |
85 |
59 |
84 |
59 |
81 |
57 |
64 |
62 |
20 |
13 |
20 |
24 |
5704 |
Blythe AP |
33.6 |
395 |
114.7 |
115 |
74 |
112 |
73 |
111 |
73 |
108 |
71 |
80 |
78 |
27 |
28 |
33 |
36 |
1219 |
Blythe CO |
33.6 |
268 |
114.6 |
115 |
74 |
112 |
73 |
111 |
73 |
108 |
71 |
80 |
78 |
27 |
24 |
29 |
32 |
1312 |
Boca |
39.4 |
5575 |
120.1 |
92 |
58 |
89 |
57 |
88 |
57 |
84 |
55 |
62 |
60 |
46 |
-18 |
-13 |
-10 |
8340 |
Bodie |
38.2 |
8370 |
119 |
83 |
50 |
80 |
49 |
79 |
49 |
76 |
48 |
55 |
53 |
42 |
-21 |
-16 |
-13 |
- |
Bonadella Ranchos – Madera Rancho |
36.8 |
270 |
119.9 |
105 |
72 |
101 |
70 |
100 |
70 |
96 |
68 |
74 |
72 |
40 |
|
29 |
32 |
1273 |
Bonita |
32.7 |
105 |
117 |
91 |
69 |
82 |
67 |
81 |
66 |
78 |
64 |
70 |
68 |
20 |
28 |
32 |
44 |
1864 |
Boron AFS |
35.1 |
3015 |
117.6 |
106 |
70 |
103 |
69 |
102 |
69 |
98 |
68 |
73 |
71 |
35 |
18 |
23 |
26 |
3000 |
Borrego Desert PK |
33.2 |
805 |
116.4 |
112 |
76 |
107 |
74 |
105 |
74 |
101 |
72 |
79 |
77 |
36 |
25 |
30 |
33 |
- |
Bostonia |
32.8 |
600 |
116.9 |
96 |
70 |
91 |
69 |
88 |
69 |
81 |
67 |
72 |
70 |
30 |
29 |
34 |
36 |
- |
Boulder Creek |
37.2 |
493 |
122.1 |
92 |
67 |
85 |
65 |
83 |
65 |
79 |
63 |
69 |
67 |
30 |
25 |
30 |
33 |
1120 |
Bowman Dam |
39.4 |
5347 |
120.7 |
89 |
59 |
86 |
57 |
85 |
57 |
82 |
55 |
63 |
60 |
26 |
9 |
17 |
22 |
5964 |
Boyes Hot Sprgs |
38.2 |
300 |
122.5 |
100 |
70 |
95 |
69 |
93 |
69 |
89 |
67 |
72 |
70 |
40 |
22 |
28 |
31 |
1289 |
Brannan Island |
38.1 |
30 |
121.7 |
100 |
69 |
95 |
68 |
93 |
68 |
89 |
67 |
72 |
70 |
10 |
24 |
28 |
31 |
- |
Brawley 2 SW |
33 |
-100 |
115.6 |
113 |
74 |
110 |
73 |
109 |
73 |
105 |
73 |
81 |
79 |
32 |
25 |
30 |
33 |
1204 |
Brea Dam |
33.9 |
275 |
117.9 |
100 |
69 |
94 |
68 |
92 |
68 |
86 |
66 |
73 |
71 |
29 |
30 |
34 |
37 |
- |
Brentwood |
37.9 |
71 |
121.7 |
102 |
70 |
97 |
68 |
95 |
67 |
89 |
65 |
71 |
68 |
34 |
27 |
32 |
35 |
- |
Bridgeport |
38.2 |
6470 |
119.2 |
89 |
56 |
86 |
54 |
85 |
54 |
82 |
53 |
60 |
57 |
41 |
-20 |
-15 |
-12 |
- |
Broderick-Bryte |
38.6 |
20 |
121.5 |
104 |
71 |
100 |
69 |
98 |
69 |
94 |
67 |
72 |
71 |
36 |
25 |
31 |
35 |
- |
Brooks Ranch |
38.8 |
294 |
122.2 |
104 |
71 |
99 |
70 |
97 |
70 |
93 |
68 |
73 |
71 |
35 |
19 |
25 |
28 |
2968 |
Buena Park |
33.9 |
75 |
118 |
98 |
69 |
92 |
68 |
90 |
68 |
85 |
67 |
72 |
70 |
25 |
31 |
35 |
38 |
- |
Burbank AP |
34.2 |
699 |
118.4 |
101 |
70 |
96 |
68 |
94 |
68 |
90 |
67 |
72 |
70 |
28 |
29 |
34 |
36 |
1701 |
Burbank Vly Pump |
34.2 |
655 |
118.4 |
101 |
69 |
96 |
68 |
94 |
68 |
90 |
66 |
72 |
70 |
28 |
29 |
34 |
36 |
1678 |
Burlingame |
37.6 |
10 |
122.4 |
88 |
67 |
82 |
64 |
80 |
64 |
76 |
63 |
68 |
65 |
20 |
30 |
35 |
37 |
- |
Burney |
40.9 |
3127 |
121.7 |
95 |
64 |
92 |
63 |
91 |
63 |
88 |
61 |
67 |
65 |
42 |
0 |
5 |
12 |
6404 |
Butler Valley (Korbel) |
40.7 |
420 |
123.9 |
91 |
66 |
86 |
64 |
85 |
64 |
81 |
62 |
67 |
65 |
22 |
20 |
26 |
29 |
- |
Buttonwillow |
35.4 |
269 |
119.5 |
103 |
71 |
99 |
70 |
98 |
70 |
95 |
68 |
74 |
72 |
36 |
20 |
26 |
29 |
2621 |
Cabrillo NM |
32.7 |
410 |
117.2 |
89 |
69 |
84 |
68 |
83 |
68 |
80 |
67 |
71 |
69 |
12 |
39 |
43 |
45 |
- |
Cachuma Lake |
34.6 |
781 |
120 |
97 |
69 |
92 |
67 |
91 |
67 |
87 |
65 |
70 |
68 |
19 |
26 |
31 |
34 |
- |
Calabasas |
34.2 |
1100 |
118.6 |
102 |
71 |
98 |
70 |
97 |
70 |
93 |
69 |
73 |
71 |
26 |
26 |
30 |
33 |
2348 |
Calaveras Big Trees |
38.3 |
4696 |
120.3 |
92 |
61 |
88 |
60 |
87 |
60 |
84 |
58 |
64 |
62 |
33 |
11 |
18 |
23 |
5848 |
Calexico |
32.7 |
12 |
115.5 |
114 |
74 |
110 |
73 |
109 |
73 |
106 |
71 |
81 |
79 |
28 |
26 |
31 |
34 |
- |
California City |
35.1 |
2400 |
118 |
107 |
69 |
104 |
68 |
103 |
68 |
99 |
66 |
72 |
70 |
33 |
10 |
17 |
22 |
2572 |
Callahan |
41.3 |
3185 |
122.8 |
97 |
63 |
93 |
62 |
92 |
62 |
88 |
60 |
66 |
64 |
35 |
7 |
15 |
20 |
- |
Calwa |
36.8 |
330 |
119.8 |
105 |
73 |
101 |
71 |
100 |
70 |
97 |
68 |
75 |
73 |
34 |
23 |
27 |
29 |
- |
Camarillo |
34.2 |
147 |
119.2 |
91 |
69 |
84 |
68 |
82 |
68 |
78 |
67 |
71 |
69 |
22 |
28 |
32 |
35 |
|
Cambria AFS |
35.5 |
690 |
121.1 |
78 |
62 |
72 |
61 |
70 |
61 |
66 |
59 |
64 |
62 |
16 |
30 |
35 |
38 |
3646 |
Cameron Park |
38.6 |
1800 |
121 |
101 |
67 |
98 |
66 |
97 |
66 |
93 |
65 |
70 |
68 |
42 |
20 |
26 |
29 |
2235 |
Camp Pardee |
38.2 |
658 |
120.9 |
106 |
71 |
103 |
70 |
102 |
70 |
98 |
69 |
74 |
72 |
36 |
27 |
32 |
35 |
2812 |
Camp Pendleton |
33.4 |
50 |
117.4 |
88 |
69 |
85 |
68 |
84 |
68 |
80 |
67 |
71 |
69 |
12 |
34 |
38 |
40 |
- |
Camp Roberts |
35.8 |
765 |
120.8 |
106 |
72 |
101 |
71 |
99 |
71 |
95 |
69 |
74 |
72 |
45 |
16 |
24 |
27 |
2890 |
Campbell |
37.3 |
195 |
121.8 |
93 |
69 |
88 |
66 |
87 |
66 |
83 |
65 |
71 |
68 |
30 |
28 |
33 |
36 |
- |
Campo |
32.6 |
2630 |
116.5 |
101 |
67 |
95 |
66 |
94 |
66 |
90 |
66 |
71 |
69 |
41 |
16 |
23 |
27 |
3303 |
Canoga Park |
34.2 |
790 |
118.6 |
104 |
71 |
99 |
70 |
97 |
70 |
93 |
69 |
74 |
72 |
38 |
25 |
30 |
33 |
1884 |
Cantil |
35.3 |
2010 |
118 |
111 |
71 |
107 |
71 |
106 |
71 |
103 |
70 |
74 |
73 |
32 |
12 |
19 |
24 |
- |
Canyon Dam |
40.1 |
4555 |
121.1 |
93 |
60 |
90 |
59 |
89 |
59 |
85 |
57 |
64 |
62 |
39 |
1 |
6 |
13 |
6834 |
Canyon Lake |
33.8 |
1500 |
117.3 |
105 |
70 |
101 |
69 |
100 |
69 |
97 |
68 |
74 |
72 |
39 |
22 |
27 |
30 |
- |
Capitola |
37 |
64 |
122 |
94 |
67 |
88 |
66 |
86 |
65 |
81 |
63 |
69 |
67 |
24 |
27 |
32 |
35 |
- |
Cardiff-by-the-Sea |
33 |
80 |
117.3 |
87 |
68 |
83 |
67 |
81 |
67 |
77 |
65 |
70 |
68 |
12 |
35 |
39 |
41 |
- |
Carlsbad |
33.2 |
44 |
117.4 |
87 |
68 |
83 |
67 |
81 |
67 |
77 |
65 |
70 |
68 |
10 |
34 |
38 |
40 |
- |
Carmel Valley |
36.5 |
425 |
121.7 |
94 |
68 |
88 |
66 |
86 |
66 |
80 |
65 |
69 |
67 |
20 |
25 |
30 |
33 |
- |
Carmel-by-the-Sea |
36.5 |
20 |
121.9 |
87 |
65 |
78 |
62 |
76 |
62 |
71 |
61 |
66 |
63 |
20 |
30 |
35 |
38 |
968 |
Carmichael |
38.6 |
100 |
121.5 |
104 |
70 |
100 |
69 |
98 |
69 |
94 |
68 |
73 |
71 |
35 |
25 |
35 |
37 |
1290 |
Carpinteria |
34.4 |
385 |
119.5 |
90 |
69 |
83 |
67 |
81 |
67 |
77 |
65 |
70 |
68 |
15 |
30 |
34 |
37 |
- |
Carson |
33.8 |
60 |
118.3 |
96 |
69 |
88 |
68 |
86 |
68 |
82 |
66 |
71 |
69 |
19 |
33 |
38 |
40 |
- |
Casa de Oro-Mount Helix |
32.7 |
530 |
117.0 |
96 |
71 |
88 |
69 |
87 |
69 |
84 |
67 |
72 |
70 |
19 |
34 |
38 |
41 |
404 |
Castle AFB |
37.4 |
188 |
120.6 |
105 |
71 |
101 |
70 |
100 |
70 |
96 |
69 |
73 |
71 |
33 |
24 |
28 |
31 |
2590 |
Castro Valley |
37.6 |
177 |
122.2 |
93 |
67 |
87 |
67 |
85 |
67 |
80 |
65 |
69 |
68 |
25 |
24 |
29 |
32 |
- |
Castroville |
36.8 |
20 |
121.8 |
86 |
66 |
77 |
63 |
75 |
63 |
70 |
61 |
67 |
64 |
18 |
32 |
37 |
40 |
1151 |
Cathedral City |
33.8 |
400 |
116.5 |
117 |
74 |
113 |
73 |
112 |
73 |
109 |
72 |
79 |
78 |
33 |
26 |
31 |
34 |
374 |
Catheys Valley |
37.4 |
1000 |
120.1 |
102 |
69 |
99 |
68 |
98 |
68 |
94 |
67 |
72 |
70 |
38 |
21 |
27 |
30 |
- |
Cecilville |
41.1 |
3000 |
123.1 |
95 |
63 |
89 |
62 |
88 |
61 |
84 |
59 |
65 |
63 |
44 |
13 |
20 |
24 |
- |
Cedarville |
41.5 |
4670 |
120.2 |
97 |
61 |
94 |
60 |
93 |
60 |
89 |
58 |
65 |
63 |
35 |
1 |
6 |
13 |
6304 |
Centerville PH |
39.8 |
522 |
121.7 |
105 |
70 |
100 |
68 |
99 |
68 |
96 |
67 |
72 |
70 |
40 |
25 |
30 |
33 |
2895 |
Ceres |
37.6 |
90 |
121 |
101 |
72 |
96 |
70 |
94 |
69 |
90 |
67 |
74 |
72 |
36 |
24 |
30 |
34 |
- |
Cerritos |
33.9 |
34 |
118.1 |
99 |
71 |
92 |
69 |
90 |
69 |
85 |
68 |
73 |
71 |
23 |
33 |
38 |
40 |
- |
Charter Oak |
34.1 |
600 |
117.9 |
101 |
70 |
97 |
69 |
95 |
69 |
91 |
68 |
74 |
72 |
34 |
29 |
34 |
36 |
- |
Chatsworth |
34.2 |
964 |
118.6 |
98 |
69 |
93 |
68 |
91 |
68 |
87 |
66 |
72 |
70 |
38 |
26 |
31 |
34 |
664 |
Cherry Valley Dam |
38 |
4765 |
119.9 |
96 |
62 |
92 |
61 |
91 |
61 |
88 |
59 |
65 |
63 |
32 |
9 |
16 |
21 |
- |
Cherryland |
37.5 |
100 |
122.1 |
93 |
67 |
86 |
66 |
84 |
66 |
79 |
64 |
69 |
67 |
24 |
26 |
31 |
37 |
- |
Chester |
40.3 |
4525 |
121.2 |
94 |
62 |
91 |
61 |
90 |
61 |
86 |
59 |
65 |
63 |
33 |
-3 |
2 |
8 |
- |
Chico Exp Sta |
39.7 |
205 |
121.8 |
105 |
70 |
102 |
69 |
100 |
69 |
96 |
68 |
72 |
71 |
37 |
22 |
27 |
30 |
2878 |
China Lake |
35.7 |
2220 |
117.7 |
112 |
70 |
108 |
68 |
107 |
68 |
104 |
68 |
74 |
72 |
33 |
15 |
22 |
25 |
2560 |
Chino |
34 |
714 |
117.7 |
104 |
70 |
100 |
69 |
98 |
69 |
94 |
68 |
74 |
72 |
35 |
27 |
32 |
35 |
- |
Chino Hills |
34.1 |
800 |
117.7 |
104 |
70 |
100 |
69 |
98 |
69 |
94 |
68 |
74 |
72 |
35 |
27 |
32 |
35 |
800 |
Chowchilla |
37 |
200 |
120.3 |
104 |
72 |
101 |
70 |
100 |
70 |
96 |
68 |
74 |
72 |
38 |
22 |
28 |
31 |
1250 |
Chula Vista |
32.6 |
9 |
117.1 |
90 |
70 |
84 |
68 |
83 |
68 |
79 |
66 |
71 |
69 |
9 |
33 |
38 |
40 |
2072 |
Citrus Heights |
38.7 |
138 |
121.5 |
104 |
71 |
100 |
70 |
98 |
70 |
94 |
68 |
74 |
72 |
36 |
24 |
26 |
29 |
- |
Claremont |
34.1 |
1201 |
117.8 |
101 |
69 |
97 |
68 |
95 |
68 |
91 |
66 |
73 |
71 |
34 |
29 |
34 |
36 |
2049 |
Clarksburg |
38.4 |
14 |
121.5 |
102 |
70 |
97 |
69 |
95 |
69 |
91 |
67 |
72 |
70 |
35 |
24 |
29 |
32 |
2971 |
Clayton |
38 |
60 |
121.9 |
102 |
70 |
97 |
68 |
95 |
67 |
89 |
65 |
71 |
68 |
34 |
27 |
32 |
35 |
- |
Clearlake Highlands |
39 |
1360 |
122.7 |
101 |
69 |
97 |
68 |
95 |
67 |
89 |
65 |
71 |
69 |
36 |
15 |
22 |
26 |
- |
Cloverdale |
38.8 |
320 |
123 |
102 |
70 |
97 |
69 |
95 |
68 |
89 |
66 |
72 |
70 |
37 |
26 |
31 |
34 |
2763 |
Clovis |
36.8 |
404 |
119.7 |
105 |
72 |
102 |
70 |
101 |
70 |
98 |
68 |
74 |
72 |
36 |
22 |
28 |
32 |
- |
Coachella |
33.7 |
-76 |
116.2 |
114 |
74 |
110 |
73 |
109 |
73 |
106 |
73 |
80 |
79 |
28 |
25 |
30 |
34 |
- |
Coalinga |
36.2 |
671 |
120.4 |
103 |
70 |
98 |
70 |
97 |
70 |
93 |
69 |
73 |
72 |
34 |
23 |
28 |
31 |
2592 |
Colfax |
39.1 |
2418 |
121 |
100 |
66 |
97 |
65 |
96 |
65 |
92 |
63 |
69 |
67 |
29 |
22 |
28 |
31 |
3424 |
Colton |
34.1 |
978 |
117.3 |
105 |
70 |
102 |
68 |
101 |
68 |
97 |
67 |
74 |
72 |
35 |
28 |
33 |
36 |
- |
Colusa |
39.2 |
60 |
122 |
103 |
72 |
100 |
70 |
98 |
70 |
94 |
68 |
74 |
71 |
36 |
23 |
29 |
31 |
2793 |
Commerce |
33.9 |
175 |
118.2 |
98 |
69 |
92 |
68 |
90 |
68 |
86 |
67 |
72 |
70 |
23 |
33 |
37 |
39 |
- |
Compton |
33.9 |
71 |
118.2 |
97 |
69 |
90 |
68 |
88 |
68 |
83 |
67 |
72 |
70 |
21 |
33 |
37 |
39 |
1606 |
Concord |
38 |
195 |
112 |
102 |
70 |
97 |
68 |
95 |
67 |
89 |
65 |
71 |
68 |
34 |
27 |
32 |
35 |
3035 |
Corcoran |
36.1 |
200 |
119.7 |
106 |
72 |
102 |
71 |
101 |
71 |
98 |
70 |
74 |
73 |
36 |
22 |
28 |
31 |
2666 |
Corning |
39.9 |
487 |
122.2 |
106 |
71 |
103 |
70 |
102 |
69 |
98 |
67 |
73 |
71 |
33 |
23 |
28 |
31 |
1330 |
Corona |
33.9 |
710 |
117.6 |
104 |
70 |
100 |
69 |
98 |
69 |
92 |
67 |
74 |
72 |
35 |
26 |
31 |
34 |
1794 |
Coronado |
32.7 |
20 |
117.2 |
89 |
69 |
82 |
67 |
80 |
67 |
76 |
65 |
70 |
68 |
10 |
36 |
39 |
41 |
1500 |
Corte Madera |
37.9 |
55 |
122.5 |
97 |
68 |
91 |
66 |
89 |
66 |
84 |
64 |
69 |
68 |
34 |
28 |
33 |
35 |
- |
Costa Mesa |
33.7 |
100 |
117.9 |
88 |
68 |
81 |
66 |
79 |
66 |
73 |
65 |
70 |
68 |
16 |
31 |
36 |
38 |
1482 |
Cotati |
38.3 |
100 |
122.7 |
99 |
69 |
94 |
68 |
93 |
68 |
89 |
66 |
71 |
69 |
32 |
24 |
28 |
30 |
1205 |
Country Club |
37.8 |
600 |
121.3 |
102 |
69 |
97 |
68 |
96 |
68 |
92 |
66 |
72 |
70 |
30 |
68 |
28 |
31 |
977 |
Covelo |
39.8 |
1385 |
123.3 |
99 |
67 |
93 |
65 |
91 |
65 |
87 |
63 |
69 |
67 |
43 |
15 |
22 |
26 |
4179 |
Covina |
34.1 |
575 |
117.9 |
101 |
70 |
97 |
69 |
95 |
69 |
91 |
68 |
74 |
72 |
34 |
29 |
34 |
36 |
- |
Crescent City |
41.8 |
40 |
124.2 |
75 |
61 |
69 |
59 |
68 |
59 |
65 |
58 |
61 |
60 |
18 |
28 |
33 |
36 |
4445 |
Crestline |
34.2 |
4900 |
117.3 |
90 |
62 |
86 |
61 |
85 |
61 |
81 |
59 |
66 |
64 |
26 |
13 |
20 |
24 |
3200 |
Crockett |
38 |
9 |
122.2 |
96 |
68 |
90 |
66 |
89 |
66 |
85 |
64 |
70 |
67 |
23 |
28 |
33 |
36 |
- |
Crows Landing |
37.4 |
140 |
121.1 |
101 |
70 |
96 |
68 |
94 |
68 |
89 |
66 |
72 |
70 |
33 |
23 |
28 |
31 |
2767 |
Cucamonga |
34.1 |
1450 |
117.6 |
103 |
69 |
99 |
68 |
97 |
67 |
93 |
65 |
73 |
71 |
31 |
29 |
34 |
36 |
- |
Cudahy |
33.9 |
130 |
118.2 |
98 |
70 |
91 |
69 |
89 |
69 |
85 |
67 |
72 |
70 |
21 |
33 |
37 |
39 |
- |
Culver City |
34 |
106 |
118.4 |
96 |
70 |
88 |
69 |
87 |
69 |
83 |
67 |
72 |
70 |
18 |
35 |
40 |
42 |
1515 |
Cupertino |
37.3 |
70 |
122 |
96 |
68 |
88 |
67 |
86 |
66 |
80 |
64 |
70 |
68 |
30 |
28 |
33 |
36 |
- |
Cuyama |
34.9 |
2255 |
116.6 |
99 |
68 |
96 |
67 |
94 |
67 |
89 |
66 |
72 |
70 |
42 |
13 |
20 |
24 |
- |
Cuyamaca |
33 |
4650 |
116.6 |
92 |
64 |
85 |
62 |
84 |
61 |
81 |
59 |
67 |
65 |
29 |
11 |
18 |
23 |
4848 |
Cypress |
33.8 |
75 |
118 |
98 |
70 |
92 |
69 |
90 |
69 |
85 |
67 |
72 |
70 |
24 |
31 |
35 |
38 |
|
Daggett AP |
34.9 |
1915 |
116.8 |
109 |
68 |
106 |
68 |
105 |
68 |
102 |
66 |
73 |
72 |
33 |
21 |
26 |
29 |
2203 |
Daly City |
37.6 |
410 |
122.5 |
84 |
65 |
78 |
62 |
77 |
62 |
73 |
61 |
66 |
63 |
16 |
34 |
37 |
39 |
- |
Dana Point |
33.5 |
100 |
117.7 |
91 |
69 |
84 |
68 |
82 |
68 |
78 |
66 |
71 |
69 |
13 |
30 |
33 |
36 |
600 |
Danville |
37.8 |
368 |
122 |
102 |
69 |
97 |
68 |
96 |
68 |
92 |
66 |
72 |
70 |
30 |
23 |
28 |
31 |
977 |
Davis |
38.5 |
60 |
121.8 |
103 |
72 |
99 |
70 |
97 |
70 |
93 |
68 |
74 |
71 |
41 |
24 |
30 |
34 |
2844 |
De Sabla |
39.9 |
2713 |
121.6 |
97 |
66 |
94 |
64 |
92 |
64 |
88 |
62 |
68 |
66 |
35 |
18 |
24 |
27 |
4237 |
Death Valley |
36.5 |
-194 |
116.9 |
121 |
77 |
118 |
76 |
117 |
76 |
114 |
74 |
81 |
79 |
28 |
27 |
33 |
37 |
1147 |
Deep Springs Clg |
37.5 |
5225 |
118 |
98 |
60 |
95 |
59 |
94 |
59 |
92 |
58 |
64 |
62 |
35 |
-3 |
2 |
8 |
|
Deer Creek PH |
39.3 |
4455 |
120.9 |
93 |
61 |
91 |
60 |
90 |
60 |
87 |
58 |
65 |
63 |
39 |
10 |
17 |
22 |
5863 |
Del Aire |
34 |
100 |
118.4 |
91 |
69 |
84 |
67 |
83 |
67 |
79 |
66 |
71 |
69 |
15 |
37 |
40 |
42 |
383 |
Delano |
35.8 |
323 |
119.3 |
106 |
71 |
102 |
70 |
101 |
70 |
98 |
69 |
74 |
72 |
36 |
22 |
25 |
28 |
- |
Denair |
37.6 |
137 |
120.8 |
100 |
70 |
95 |
69 |
93 |
69 |
89 |
67 |
72 |
70 |
38 |
22 |
28 |
31 |
2974 |
Desert Hot Springs |
34 |
1060 |
116.5 |
115 |
73 |
111 |
72 |
110 |
72 |
107 |
71 |
78 |
77 |
35 |
24 |
29 |
32 |
400 |
Diamond Bar |
34 |
880 |
117.8 |
101 |
69 |
97 |
68 |
96 |
68 |
92 |
66 |
73 |
71 |
33 |
28 |
33 |
35 |
- |
Dinuba |
36.5 |
340 |
119.4 |
104 |
73 |
101 |
70 |
100 |
70 |
96 |
69 |
75 |
73 |
36 |
24 |
30 |
34 |
- |
Discovery Bay |
38.1 |
10 |
121.6 |
102 |
70 |
97 |
68 |
95 |
67 |
89 |
65 |
71 |
68 |
34 |
27 |
32 |
35 |
- |
Dixon |
38.4 |
100 |
121.9 |
104 |
72 |
99 |
70 |
97 |
70 |
93 |
68 |
74 |
71 |
36 |
24 |
30 |
33 |
2826 |
Dobbins |
39.4 |
1640 |
121.2 |
104 |
70 |
101 |
68 |
100 |
68 |
96 |
67 |
72 |
70 |
31 |
24 |
29 |
32 |
- |
Donner Mem Stt Pk |
39.3 |
5937 |
120.3 |
85 |
56 |
82 |
56 |
81 |
56 |
77 |
54 |
60 |
58 |
40 |
-3 |
3 |
6 |
- |
Donner Summit |
39.4 |
7239 |
120.3 |
80 |
53 |
77 |
53 |
76 |
52 |
72 |
50 |
57 |
55 |
40 |
-8 |
-1 |
3 |
8290 |
Downey |
33.9 |
110 |
118 |
98 |
71 |
90 |
70 |
88 |
70 |
84 |
68 |
73 |
71 |
21 |
32 |
37 |
39 |
- |
Downieville RS |
39.6 |
2895 |
120.8 |
98 |
64 |
95 |
63 |
94 |
63 |
90 |
61 |
68 |
66 |
42 |
13 |
20 |
24 |
- |
Doyle |
40 |
4390 |
120.1 |
96 |
63 |
93 |
62 |
92 |
61 |
88 |
59 |
66 |
64 |
42 |
0 |
5 |
12 |
- |
Dry Canyon Res |
34.5 |
1455 |
118.5 |
105 |
71 |
100 |
69 |
99 |
69 |
96 |
68 |
74 |
72 |
32 |
24 |
29 |
32 |
- |
Duarte |
34.1 |
500 |
118 |
100 |
69 |
96 |
68 |
94 |
68 |
90 |
67 |
73 |
71 |
33 |
31 |
36 |
38 |
- |
Dublin |
37.7 |
200 |
121.5 |
99 |
69 |
93 |
67 |
91 |
67 |
86 |
65 |
70 |
68 |
35 |
24 |
29 |
32 |
- |
Dudleys |
37.7 |
3000 |
120.1 |
97 |
65 |
94 |
64 |
93 |
64 |
90 |
62 |
68 |
66 |
44 |
10 |
17 |
22 |
4959 |
Duttons Landing |
38.2 |
20 |
122.3 |
96 |
68 |
91 |
66 |
89 |
66 |
84 |
64 |
70 |
68 |
31 |
26 |
31 |
34 |
- |
Eagle Mtn |
33.8 |
973 |
115.5 |
113 |
72 |
110 |
71 |
109 |
71 |
105 |
69 |
77 |
75 |
24 |
32 |
37 |
39 |
1138 |
Earlimart |
35.8 |
283 |
119.3 |
106 |
71 |
102 |
70 |
101 |
70 |
98 |
69 |
74 |
72 |
36 |
23 |
26 |
29 |
1100 |
East Compton |
34 |
71 |
118.2 |
97 |
69 |
90 |
68 |
88 |
68 |
83 |
67 |
72 |
70 |
21 |
33 |
37 |
39 |
436 |
East Hemet |
33.7 |
1655 |
116.9 |
109 |
70 |
104 |
69 |
103 |
69 |
101 |
67 |
74 |
72 |
40 |
20 |
25 |
28 |
- |
East La Mirada |
33.9 |
115 |
118.0 |
99 |
70 |
91 |
69 |
89 |
69 |
85 |
68 |
73 |
71 |
26 |
31 |
36 |
38 |
- |
East Los Angeles |
34 |
250 |
118.3 |
99 |
69 |
92 |
68 |
90 |
68 |
86 |
67 |
72 |
70 |
21 |
38 |
41 |
43 |
- |
East Palo Alto |
37.5 |
25 |
122.1 |
93 |
66 |
85 |
64 |
83 |
64 |
77 |
62 |
68 |
66 |
25 |
26 |
31 |
34 |
1103 |
East Park Res |
39.4 |
1205 |
122.5 |
101 |
69 |
97 |
68 |
96 |
68 |
92 |
66 |
71 |
69 |
38 |
19 |
25 |
28 |
3455 |
East Pasadena |
34.2 |
864 |
118.1 |
99 |
69 |
94 |
68 |
92 |
68 |
88 |
67 |
73 |
71 |
30 |
32 |
37 |
40 |
452 |
East Porterville |
36.1 |
393 |
119.0 |
106 |
71 |
102 |
70 |
101 |
70 |
97 |
69 |
74 |
72 |
36 |
25 |
30 |
33 |
1129 |
East San Gabriel |
34.1 |
450 |
118.1 |
99 |
70 |
94 |
69 |
92 |
69 |
88 |
68 |
73 |
71 |
30 |
30 |
35 |
37 |
431 |
Edwards AFB |
34.9 |
2316 |
117.9 |
107 |
69 |
104 |
68 |
103 |
68 |
99 |
66 |
72 |
70 |
35 |
10 |
17 |
22 |
3123 |
El Cajon |
32.7 |
525 |
117 |
96 |
70 |
91 |
69 |
90 |
69 |
87 |
67 |
72 |
70 |
30 |
29 |
34 |
36 |
- |
El Capitan Dam |
32.9 |
600 |
116.8 |
105 |
71 |
98 |
70 |
97 |
70 |
93 |
68 |
74 |
72 |
35 |
29 |
34 |
36 |
1533 |
El Centro |
32.8 |
-30 |
115.6 |
115 |
74 |
111 |
73 |
110 |
73 |
107 |
73 |
81 |
79 |
34 |
26 |
35 |
38 |
1212 |
El Cerrito |
37.8 |
70 |
122.3 |
91 |
66 |
84 |
64 |
81 |
64 |
75 |
62 |
68 |
65 |
17 |
30 |
35 |
38 |
- |
El Dorado Hills |
38.6 |
673 |
121.1 |
103 |
70 |
100 |
69 |
98 |
69 |
94 |
67 |
72 |
71 |
36 |
24 |
30 |
34 |
- |
El Mirage |
34.6 |
2910 |
117.6 |
105 |
69 |
101 |
68 |
100 |
68 |
97 |
66 |
72 |
70 |
31 |
9 |
16 |
21 |
- |
El Monte |
34.1 |
271 |
118 |
101 |
71 |
97 |
70 |
95 |
70 |
91 |
68 |
73 |
71 |
30 |
31 |
36 |
39 |
- |
El Paso de Robles |
35.6 |
721 |
120.7 |
102 |
65 |
95 |
65 |
94 |
65 |
90 |
65 |
69 |
67 |
44 |
16 |
20 |
23 |
1768 |
El Rio |
34.3 |
50 |
119.2 |
95 |
69 |
88 |
68 |
86 |
68 |
82 |
66 |
71 |
69 |
20 |
30 |
34 |
37 |
- |
El Segundo |
33.9 |
105 |
118.4 |
91 |
69 |
84 |
68 |
83 |
68 |
79 |
66 |
71 |
69 |
14 |
37 |
40 |
42 |
- |
El Sobrante |
37.9 |
55 |
122.3 |
91 |
66 |
87 |
65 |
86 |
65 |
82 |
64 |
69 |
67 |
25 |
30 |
35 |
38 |
823 |
El Toro MCAS |
33.7 |
380 |
117.7 |
96 |
69 |
89 |
69 |
87 |
69 |
82 |
68 |
73 |
71 |
26 |
34 |
38 |
41 |
1591 |
El Toro Station |
33.7 |
380 |
117.7 |
96 |
69 |
89 |
69 |
87 |
69 |
82 |
68 |
73 |
71 |
26 |
34 |
38 |
41 |
560 |
Electra PH |
38.3 |
715 |
120.7 |
106 |
70 |
102 |
69 |
101 |
69 |
98 |
68 |
73 |
71 |
41 |
23 |
28 |
31 |
2858 |
Elk Grove |
38.4 |
50 |
121.4 |
104 |
71 |
100 |
69 |
98 |
69 |
94 |
68 |
73 |
71 |
35 |
29 |
34 |
36 |
1150 |
Elk Valley |
42 |
1705 |
123.7 |
96 |
65 |
90 |
63 |
88 |
63 |
84 |
61 |
67 |
65 |
39 |
16 |
23 |
27 |
5404 |
Elsinore |
33.7 |
1285 |
117.3 |
105 |
71 |
101 |
70 |
100 |
70 |
98 |
69 |
74 |
72 |
39 |
22 |
26 |
29 |
2128 |
Encinitas |
33 |
50 |
117.3 |
87 |
68 |
83 |
67 |
81 |
67 |
77 |
65 |
70 |
68 |
10 |
35 |
39 |
41 |
- |
Encino |
34.2 |
750 |
118.5 |
103 |
71 |
98 |
69 |
96 |
69 |
92 |
67 |
74 |
71 |
27 |
28 |
33 |
36 |
664 |
Enterprise |
40.6 |
470 |
122.3 |
107 |
69 |
103 |
68 |
101 |
68 |
97 |
67 |
72 |
70 |
29 |
26 |
31 |
34 |
- |
Escondido |
33.1 |
660 |
117.1 |
97 |
69 |
90 |
68 |
88 |
68 |
84 |
67 |
72 |
70 |
29 |
26 |
31 |
34 |
2005 |
Eureka |
40.8 |
43 |
124.2 |
75 |
61 |
69 |
59 |
68 |
59 |
65 |
58 |
61 |
60 |
11 |
30 |
35 |
38 |
4679 |
Exeter |
36.3 |
350 |
119.1 |
104 |
72 |
101 |
71 |
100 |
71 |
97 |
69 |
74 |
72 |
39 |
24 |
29 |
32 |
1236 |
Fair Oaks |
38.7 |
50 |
121.3 |
104 |
70 |
100 |
69 |
98 |
69 |
94 |
69 |
72 |
71 |
36 |
23 |
29 |
33 |
- |
Fairfax |
38 |
110 |
122.6 |
96 |
68 |
90 |
66 |
88 |
65 |
83 |
63 |
71 |
68 |
34 |
26 |
31 |
34 |
- |
Fairfield FS |
38.3 |
38 |
122 |
103 |
69 |
98 |
68 |
96 |
68 |
91 |
66 |
73 |
71 |
34 |
24 |
30 |
33 |
2686 |
Fairmont |
34.7 |
3060 |
118.4 |
100 |
67 |
96 |
66 |
95 |
66 |
92 |
65 |
71 |
69 |
22 |
22 |
28 |
31 |
3330 |
Fairview |
35.9 |
3519 |
118.5 |
97 |
67 |
94 |
66 |
93 |
66 |
90 |
64 |
70 |
68 |
43 |
11 |
18 |
23 |
- |
Fallbrook |
33.6 |
660 |
117.3 |
94 |
68 |
89 |
67 |
88 |
67 |
85 |
66 |
71 |
69 |
29 |
26 |
31 |
34 |
2077 |
Farmersville |
36.3 |
350 |
119.2 |
104 |
72 |
101 |
72 |
100 |
71 |
97 |
69 |
74 |
72 |
39 |
24 |
29 |
32 |
1236 |
Felton |
37 |
100 |
122.1 |
94 |
68 |
88 |
66 |
86 |
66 |
81 |
64 |
69 |
67 |
28 |
27 |
32 |
35 |
1097 |
Ferndale |
40.5 |
1445 |
124.3 |
76 |
57 |
66 |
56 |
65 |
56 |
62 |
54 |
59 |
57 |
12 |
28 |
33 |
35 |
- |
Fillmore |
34.4 |
435 |
118.9 |
100 |
70 |
94 |
69 |
92 |
69 |
87 |
67 |
73 |
71 |
30 |
28 |
32 |
35 |
- |
Five Points |
36.4 |
285 |
120.2 |
103 |
71 |
99 |
70 |
97 |
70 |
93 |
68 |
73 |
71 |
36 |
21 |
27 |
30 |
- |
Fleming Fish & Game |
40.4 |
4000 |
120.3 |
96 |
62 |
93 |
61 |
92 |
61 |
88 |
59 |
66 |
64 |
40 |
-3 |
2 |
8 |
- |
Florence-Graham |
34 |
175 |
118.3 |
98 |
69 |
90 |
68 |
88 |
68 |
84 |
67 |
72 |
70 |
19 |
35 |
40 |
43 |
- |
Florin |
38.5 |
100 |
121.4 |
104 |
71 |
100 |
69 |
98 |
69 |
94 |
68 |
73 |
71 |
35 |
29 |
34 |
36 |
- |
Folsom Dam |
38.7 |
350 |
121.2 |
104 |
70 |
101 |
69 |
99 |
69 |
95 |
67 |
72 |
71 |
36 |
25 |
31 |
35 |
- |
Fontana |
34.1 |
1090 |
117.4 |
105 |
70 |
101 |
69 |
100 |
69 |
97 |
67 |
74 |
72 |
33 |
30 |
35 |
38 |
1530 |
Foothill Farms |
38.6 |
90 |
121.3 |
104 |
71 |
100 |
70 |
98 |
70 |
94 |
68 |
73 |
71 |
36 |
24 |
30 |
34 |
- |
Forest Glen |
40.4 |
2340 |
123.3 |
96 |
65 |
92 |
64 |
91 |
64 |
88 |
62 |
67 |
65 |
42 |
12 |
19 |
24 |
- |
Fort Baker |
37.8 |
15 |
122.5 |
87 |
66 |
81 |
65 |
79 |
65 |
73 |
65 |
67 |
65 |
12 |
33 |
38 |
40 |
3080 |
Fort Bidwell |
41.9 |
4498 |
120.1 |
93 |
60 |
90 |
59 |
89 |
59 |
85 |
57 |
64 |
62 |
38 |
-2 |
3 |
10 |
6381 |
Fort Bragg |
39.5 |
80 |
123.8 |
75 |
60 |
67 |
59 |
66 |
59 |
62 |
58 |
62 |
61 |
15 |
29 |
34 |
37 |
4424 |
Fort Jones RS |
41.6 |
2725 |
122.9 |
98 |
64 |
93 |
63 |
92 |
63 |
88 |
61 |
67 |
65 |
44 |
5 |
13 |
18 |
5590 |
Fort MacArthur |
33.7 |
200 |
118.3 |
92 |
69 |
84 |
68 |
82 |
68 |
78 |
66 |
71 |
69 |
13 |
35 |
40 |
42 |
1819 |
Fort Ord |
36.7 |
134 |
121.8 |
86 |
65 |
77 |
63 |
75 |
62 |
70 |
60 |
67 |
64 |
18 |
24 |
29 |
32 |
3818 |
Fort Ross |
38.5 |
116 |
123.3 |
79 |
63 |
74 |
62 |
71 |
61 |
65 |
59 |
64 |
62 |
19 |
30 |
35 |
37 |
4127 |
Fortuna |
40.6 |
100 |
124.2 |
75 |
61 |
69 |
59 |
68 |
59 |
65 |
58 |
61 |
60 |
11 |
30 |
35 |
38 |
2000 |
Foster City |
37.5 |
20 |
122.7 |
92 |
67 |
84 |
65 |
82 |
65 |
76 |
63 |
68 |
66 |
22 |
29 |
34 |
36 |
- |
Fountain Valley |
33.7 |
60 |
118 |
97 |
70 |
90 |
68 |
88 |
68 |
84 |
67 |
72 |
70 |
18 |
33 |
38 |
40 |
- |
Freedom |
37 |
1495 |
121.8 |
89 |
67 |
85 |
64 |
83 |
64 |
79 |
62 |
68 |
65 |
22 |
27 |
32 |
34 |
- |
Fremont |
37.5 |
56 |
122 |
94 |
67 |
88 |
65 |
86 |
65 |
81 |
63 |
69 |
67 |
24 |
25 |
30 |
33 |
- |
Fresno AP |
36.8 |
328 |
119.7 |
104 |
73 |
101 |
71 |
100 |
70 |
97 |
68 |
75 |
73 |
34 |
24 |
28 |
30 |
2650 |
Friant Gov Camp |
37 |
410 |
119.7 |
106 |
72 |
103 |
70 |
102 |
70 |
100 |
68 |
74 |
72 |
40 |
23 |
28 |
31 |
2768 |
Fullerton |
33.9 |
340 |
117.9 |
100 |
70 |
94 |
69 |
92 |
69 |
87 |
68 |
73 |
71 |
26 |
30 |
35 |
37 |
- |
Galt |
38.2 |
40 |
121.3 |
101 |
70 |
97 |
68 |
95 |
68 |
91 |
67 |
72 |
70 |
38 |
23 |
28 |
31 |
1240 |
Garden Acres |
38 |
20 |
121.3 |
103 |
71 |
98 |
69 |
97 |
69 |
93 |
67 |
73 |
71 |
35 |
24 |
28 |
30 |
1334 |
Garden Grove |
33.6 |
85 |
117.9 |
98 |
70 |
91 |
68 |
89 |
68 |
84 |
67 |
72 |
70 |
23 |
31 |
36 |
38 |
- |
Gardena |
33.9 |
40 |
118.3 |
92 |
69 |
85 |
68 |
84 |
68 |
80 |
66 |
71 |
69 |
18 |
32 |
37 |
39 |
- |
George AFB |
34.6 |
2875 |
117.4 |
105 |
67 |
102 |
65 |
101 |
64 |
98 |
62 |
70 |
68 |
31 |
19 |
23 |
26 |
2887 |
Georgetown RS |
38.9 |
3001 |
120.8 |
98 |
64 |
95 |
63 |
94 |
63 |
90 |
61 |
68 |
66 |
31 |
18 |
24 |
27 |
- |
Giant Forest |
36.6 |
6412 |
118.8 |
84 |
56 |
81 |
55 |
80 |
55 |
77 |
53 |
60 |
58 |
26 |
5 |
13 |
18 |
- |
Gillespie Field |
32.8 |
385 |
117.0 |
98 |
71 |
91 |
70 |
89 |
70 |
85 |
68 |
73 |
71 |
30 |
24 |
29 |
32 |
- |
Gilroy |
37 |
194 |
121.6 |
101 |
70 |
93 |
68 |
91 |
67 |
86 |
65 |
72 |
69 |
25 |
23 |
28 |
31 |
- |
Glen Avon |
34 |
827 |
117.5 |
105 |
70 |
101 |
69 |
99 |
69 |
95 |
67 |
74 |
72 |
35 |
28 |
33 |
35 |
- |
Glendale |
34.2 |
563 |
118.3 |
101 |
70 |
96 |
68 |
94 |
68 |
90 |
67 |
73 |
71 |
28 |
30 |
35 |
37 |
- |
Glendora |
34.1 |
822 |
117.9 |
102 |
69 |
98 |
68 |
96 |
68 |
92 |
67 |
73 |
71 |
35 |
30 |
35 |
37 |
- |
Glennville |
35.7 |
3140 |
118.7 |
97 |
67 |
94 |
66 |
93 |
66 |
90 |
64 |
70 |
68 |
43 |
11 |
18 |
23 |
4423 |
Gold Rock Rch |
32.9 |
485 |
114.8 |
113 |
73 |
110 |
72 |
109 |
72 |
106 |
70 |
79 |
77 |
28 |
31 |
36 |
38 |
- |
Golden Hills |
35.1 |
4000 |
118.5 |
97 |
66 |
93 |
65 |
92 |
65 |
89 |
64 |
69 |
67 |
33 |
13 |
20 |
24 |
- |
Granada Hills |
34.4 |
1032 |
118.5 |
100 |
70 |
95 |
68 |
93 |
68 |
89 |
66 |
73 |
70 |
37 |
28 |
31 |
34 |
664 |
Grand Terrace |
34.1 |
1000 |
117.3 |
105 |
70 |
102 |
68 |
101 |
68 |
97 |
67 |
74 |
72 |
35 |
28 |
33 |
36 |
611 |
Grant Grove |
36.7 |
6600 |
119 |
82 |
56 |
78 |
55 |
77 |
54 |
74 |
52 |
59 |
57 |
26 |
6 |
14 |
19 |
7044 |
Grass Valley |
39.2 |
2400 |
121.1 |
99 |
67 |
96 |
65 |
95 |
65 |
91 |
63 |
69 |
67 |
29 |
19 |
25 |
28 |
- |
Graton |
38.4 |
200 |
122.9 |
95 |
68 |
91 |
67 |
88 |
66 |
82 |
64 |
70 |
68 |
34 |
22 |
28 |
31 |
3409 |
Greenacres |
35.3 |
400 |
119.1 |
106 |
71 |
102 |
70 |
101 |
70 |
98 |
68 |
74 |
72 |
34 |
26 |
31 |
35 |
934 |
Greenfield |
36.2 |
287 |
121.2 |
92 |
67 |
88 |
65 |
87 |
65 |
84 |
64 |
70 |
68 |
32 |
22 |
27 |
30 |
1020 |
Grossmont |
32.7 |
530 |
117 |
96 |
69 |
89 |
68 |
88 |
68 |
84 |
66 |
71 |
69 |
23 |
31 |
36 |
38 |
- |
Grover City |
35.1 |
100 |
120.6 |
93 |
69 |
86 |
64 |
84 |
64 |
80 |
62 |
67 |
65 |
18 |
30 |
34 |
37 |
- |
Guadalupe |
35 |
85 |
120.6 |
92 |
66 |
86 |
64 |
84 |
64 |
79 |
62 |
67 |
65 |
18 |
28 |
32 |
35 |
1035 |
Hacienda Hts |
34 |
300 |
118 |
100 |
69 |
96 |
68 |
94 |
68 |
90 |
67 |
73 |
71 |
28 |
31 |
36 |
38 |
- |
Haiwee |
36.1 |
3825 |
118 |
102 |
65 |
99 |
64 |
98 |
64 |
95 |
62 |
68 |
66 |
27 |
15 |
22 |
26 |
3700 |
Half Moon Bay |
37.5 |
60 |
122.4 |
83 |
64 |
76 |
62 |
74 |
61 |
69 |
59 |
65 |
63 |
15 |
32 |
37 |
39 |
3843 |
Hamilton AFB |
38.1 |
3 |
122.5 |
95 |
69 |
88 |
67 |
86 |
67 |
81 |
65 |
73 |
70 |
28 |
27 |
30 |
32 |
3311 |
Hanford |
36.3 |
242 |
119.7 |
102 |
71 |
99 |
70 |
98 |
70 |
94 |
68 |
73 |
71 |
37 |
22 |
28 |
31 |
2736 |
Happy Camp RS |
41.8 |
1150 |
123.4 |
103 |
67 |
97 |
66 |
96 |
66 |
92 |
65 |
69 |
67 |
41 |
18 |
24 |
27 |
4263 |
Hat Creek PH 1 |
40.9 |
3015 |
121.6 |
99 |
65 |
96 |
64 |
95 |
64 |
91 |
62 |
68 |
66 |
48 |
2 |
7 |
17 |
5689 |
Hawaiian Gardens |
33.8 |
75 |
118.1 |
97 |
70 |
91 |
69 |
89 |
69 |
84 |
67 |
72 |
70 |
23 |
32 |
37 |
39 |
- |
Hawthorne |
33.9 |
70 |
118.4 |
92 |
69 |
85 |
68 |
84 |
68 |
80 |
66 |
71 |
69 |
16 |
37 |
40 |
42 |
- |
Hayfield Pumps |
33.7 |
1370 |
115.6 |
112 |
71 |
108 |
70 |
107 |
70 |
104 |
68 |
77 |
75 |
31 |
24 |
29 |
32 |
1529 |
Hayward |
37.7 |
530 |
122.1 |
92 |
66 |
86 |
65 |
85 |
64 |
81 |
62 |
68 |
66 |
24 |
26 |
31 |
34 |
2909 |
Healdsburg |
38.6 |
102 |
122.9 |
102 |
69 |
95 |
68 |
94 |
68 |
90 |
66 |
71 |
69 |
37 |
26 |
31 |
34 |
2572 |
Hemet |
33.7 |
1655 |
117 |
109 |
70 |
104 |
69 |
103 |
69 |
101 |
67 |
74 |
72 |
40 |
20 |
25 |
28 |
- |
Henshaw Dam |
33.2 |
2700 |
116.8 |
99 |
68 |
94 |
67 |
93 |
67 |
90 |
66 |
71 |
69 |
38 |
15 |
22 |
26 |
3708 |
Hercules |
38 |
15 |
122.3 |
91 |
66 |
87 |
65 |
86 |
65 |
82 |
64 |
69 |
67 |
25 |
30 |
35 |
38 |
823 |
Hermosa Beach |
33.9 |
16 |
118.4 |
92 |
69 |
84 |
68 |
82 |
68 |
78 |
66 |
71 |
69 |
12 |
38 |
42 |
45 |
- |
Hesperia |
34.4 |
3191 |
117.3 |
105 |
67 |
101 |
65 |
100 |
65 |
97 |
63 |
70 |
68 |
38 |
14 |
21 |
25 |
1654 |
Hetch Hetchy |
38 |
3870 |
119.8 |
93 |
62 |
89 |
61 |
88 |
61 |
85 |
59 |
65 |
63 |
32 |
14 |
21 |
25 |
4816 |
Highland |
34.1 |
1315 |
117.2 |
106 |
70 |
102 |
69 |
101 |
69 |
97 |
68 |
74 |
72 |
36 |
26 |
31 |
34 |
- |
Hillcrest Center |
35.4 |
500 |
- |
106 |
71 |
102 |
70 |
101 |
70 |
98 |
68 |
74 |
72 |
34 |
26 |
31 |
35 |
- |
Hillsborough |
37.6 |
352 |
122.3 |
90 |
66 |
82 |
65 |
80 |
65 |
74 |
64 |
68 |
66 |
23 |
30 |
35 |
37 |
- |
Hilt |
42 |
2900 |
122.6 |
97 |
64 |
93 |
62 |
92 |
62 |
89 |
60 |
66 |
64 |
39 |
5 |
13 |
18 |
- |
Hollister |
36.9 |
280 |
121.4 |
96 |
68 |
89 |
67 |
87 |
67 |
81 |
65 |
70 |
68 |
30 |
21 |
27 |
30 |
2725 |
Hollywood |
34 |
384 |
118.4 |
96 |
70 |
89 |
69 |
87 |
69 |
83 |
67 |
72 |
70 |
20 |
36 |
41 |
44 |
- |
Home Gardens |
33.9 |
678 |
117.5 |
104 |
70 |
100 |
69 |
98 |
69 |
92 |
67 |
74 |
72 |
35 |
26 |
31 |
34 |
- |
Hoopa |
41 |
360 |
123.7 |
100 |
67 |
92 |
66 |
91 |
66 |
87 |
64 |
69 |
67 |
25 |
23 |
28 |
31 |
- |
Huntington Beach |
33.7 |
40 |
117.8 |
91 |
69 |
83 |
67 |
81 |
67 |
76 |
66 |
71 |
69 |
14 |
34 |
38 |
41 |
- |
Huntington Lake |
37.2 |
7020 |
119.2 |
80 |
55 |
77 |
54 |
76 |
53 |
73 |
51 |
58 |
56 |
25 |
3 |
11 |
16 |
7632 |
Huntington Park |
34 |
175 |
118 |
98 |
70 |
90 |
69 |
88 |
69 |
84 |
67 |
72 |
70 |
20 |
38 |
42 |
45 |
- |
Idlewild |
41.9 |
1250 |
124 |
103 |
68 |
96 |
66 |
95 |
66 |
92 |
65 |
69 |
67 |
40 |
18 |
24 |
27 |
- |
Idria |
36.4 |
2650 |
120.7 |
97 |
66 |
92 |
65 |
91 |
64 |
87 |
62 |
68 |
66 |
27 |
24 |
29 |
32 |
3128 |
Idyllwild |
33.7 |
5397 |
116.7 |
93 |
62 |
89 |
61 |
88 |
61 |
84 |
60 |
67 |
65 |
35 |
9 |
16 |
21 |
- |
Imperial AP |
32.8 |
-59 |
115.6 |
114 |
74 |
110 |
73 |
109 |
73 |
106 |
72 |
81 |
79 |
31 |
26 |
31 |
34 |
1060 |
Imperial Beach |
32.5 |
23 |
117.1 |
87 |
69 |
82 |
68 |
81 |
68 |
78 |
67 |
71 |
69 |
10 |
35 |
39 |
41 |
1839 |
Imperial CO |
32.9 |
-64 |
115.6 |
112 |
73 |
108 |
72 |
107 |
72 |
104 |
71 |
80 |
78 |
31 |
29 |
34 |
36 |
976 |
Independence |
36.8 |
3950 |
118.2 |
104 |
61 |
101 |
60 |
100 |
60 |
97 |
60 |
65 |
63 |
31 |
12 |
19 |
24 |
- |
Indio |
33.7 |
11 |
116.3 |
115 |
75 |
112 |
75 |
111 |
75 |
107 |
74 |
81 |
79 |
30 |
24 |
29 |
32 |
1059 |
Inglewood |
33.9 |
105 |
118 |
92 |
68 |
85 |
67 |
84 |
67 |
80 |
65 |
70 |
68 |
15 |
37 |
40 |
42 |
- |
Inyokern NAS |
35.7 |
2440 |
117.8 |
110 |
71 |
106 |
68 |
105 |
68 |
102 |
66 |
75 |
71 |
37 |
15 |
22 |
26 |
2772 |
Ione |
38.3 |
298 |
120.9 |
101 |
70 |
97 |
68 |
95 |
68 |
91 |
67 |
72 |
70 |
38 |
23 |
28 |
31 |
- |
Iron Mtn |
34.1 |
922 |
115.1 |
116 |
75 |
112 |
74 |
111 |
74 |
108 |
73 |
80 |
78 |
26 |
29 |
34 |
36 |
1251 |
Irvine |
33.7 |
50 |
118 |
96 |
69 |
88 |
68 |
86 |
68 |
82 |
67 |
72 |
70 |
27 |
33 |
37 |
40 |
- |
Isla Vista |
34.5 |
40 |
119.9 |
90 |
69 |
83 |
67 |
81 |
67 |
77 |
65 |
70 |
68 |
20 |
33 |
38 |
40 |
- |
Jess Valley |
41.3 |
5300 |
120.3 |
92 |
59 |
89 |
58 |
88 |
58 |
84 |
56 |
63 |
61 |
35 |
-7 |
-2 |
4 |
7045 |
John Wayne AP |
33.6 |
115 |
117.9 |
98 |
70 |
91 |
68 |
89 |
68 |
84 |
67 |
72 |
70 |
26 |
33 |
37 |
39 |
1496 |
Julian Wynola |
33.1 |
3650 |
116.8 |
96 |
66 |
91 |
64 |
90 |
64 |
87 |
62 |
69 |
67 |
39 |
20 |
24 |
26 |
4049 |
Kentfield |
38 |
120 |
122.6 |
97 |
66 |
91 |
65 |
89 |
65 |
84 |
63 |
70 |
68 |
35 |
27 |
32 |
35 |
3009 |
Kerman |
36.6 |
216 |
120.1 |
105 |
73 |
101 |
71 |
100 |
70 |
97 |
68 |
75 |
73 |
34 |
24 |
28 |
30 |
1262 |
Kern River PH 1 |
35.5 |
970 |
118.8 |
106 |
72 |
103 |
71 |
102 |
71 |
99 |
69 |
75 |
73 |
26 |
30 |
35 |
37 |
1878 |
Kern River PH 3 |
35.8 |
2703 |
118.6 |
103 |
69 |
100 |
68 |
99 |
68 |
96 |
66 |
72 |
70 |
34 |
19 |
25 |
28 |
2891 |
Kettleman Stn |
36.1 |
508 |
120.1 |
104 |
71 |
100 |
70 |
98 |
70 |
93 |
68 |
74 |
72 |
31 |
26 |
31 |
34 |
2180 |
King City |
36.2 |
320 |
121.1 |
94 |
67 |
90 |
65 |
89 |
65 |
85 |
64 |
70 |
68 |
36 |
20 |
26 |
29 |
2639 |
Kingsburg |
36.4 |
297 |
119.6 |
104 |
73 |
101 |
71 |
100 |
71 |
97 |
69 |
75 |
73 |
36 |
24 |
30 |
34 |
1300 |
Klamath |
41.5 |
25 |
124.1 |
79 |
62 |
71 |
60 |
70 |
60 |
66 |
58 |
64 |
61 |
18 |
26 |
31 |
33 |
4509 |
Knights Ferry |
37.8 |
315 |
120.6 |
103 |
70 |
99 |
68 |
98 |
68 |
94 |
67 |
73 |
71 |
37 |
19 |
25 |
28 |
- |
La Canada-Flintridge |
34.2 |
1365 |
118 |
99 |
69 |
95 |
68 |
93 |
68 |
88 |
66 |
72 |
70 |
30 |
32 |
36 |
38 |
- |
La Crescenta-Montrose |
34.2 |
1565 |
118 |
98 |
69 |
94 |
68 |
92 |
68 |
87 |
66 |
72 |
70 |
33 |
31 |
35 |
37 |
- |
La Habra |
33.9 |
305 |
118 |
100 |
69 |
94 |
68 |
92 |
68 |
87 |
67 |
72 |
70 |
27 |
30 |
35 |
37 |
- |
La Habra Heights |
34 |
400 |
118 |
100 |
69 |
94 |
68 |
92 |
68 |
87 |
67 |
72 |
70 |
27 |
30 |
35 |
37 |
- |
La Mesa |
32.8 |
530 |
117 |
94 |
70 |
88 |
69 |
87 |
69 |
84 |
67 |
72 |
70 |
23 |
34 |
39 |
41 |
1567 |
La Mirada |
33.9 |
115 |
118 |
99 |
70 |
91 |
69 |
89 |
69 |
85 |
68 |
73 |
71 |
26 |
31 |
36 |
38 |
- |
La Palma |
33.9 |
75 |
118 |
98 |
69 |
92 |
68 |
90 |
68 |
85 |
67 |
72 |
70 |
25 |
31 |
35 |
38 |
- |
La Puente |
34 |
320 |
118 |
101 |
71 |
97 |
70 |
95 |
70 |
91 |
69 |
74 |
72 |
28 |
31 |
36 |
38 |
- |
La Quinta |
33.8 |
400 |
116.3 |
116 |
74 |
112 |
73 |
111 |
73 |
108 |
72 |
79 |
78 |
34 |
26 |
32 |
34 |
332 |
La Riviera |
38.6 |
190 |
121.3 |
104 |
71 |
100 |
70 |
98 |
70 |
94 |
68 |
73 |
71 |
32 |
30 |
35 |
37 |
1025 |
La Verne |
34.1 |
1235 |
118 |
101 |
69 |
97 |
68 |
95 |
68 |
91 |
67 |
73 |
71 |
34 |
29 |
34 |
36 |
- |
Ladera Heights |
34.1 |
100 |
118.4 |
91 |
67 |
84 |
67 |
83 |
67 |
79 |
66 |
71 |
69 |
14 |
37 |
40 |
42 |
383 |
Lafayette |
37.9 |
535 |
122.1 |
100 |
69 |
94 |
67 |
92 |
67 |
87 |
66 |
71 |
69 |
32 |
24 |
29 |
32 |
- |
Laguna Beach |
33.5 |
35 |
117.8 |
91 |
69 |
83 |
68 |
81 |
68 |
76 |
66 |
71 |
69 |
18 |
30 |
33 |
36 |
2222 |
Laguna Niguel |
33.6 |
500 |
117.7 |
95 |
67 |
87 |
66 |
85 |
65 |
81 |
63 |
71 |
67 |
22 |
33 |
37 |
40 |
- |
Lake Arrowhead |
34.2 |
5205 |
117.2 |
90 |
62 |
86 |
61 |
85 |
61 |
81 |
59 |
66 |
64 |
26 |
13 |
20 |
24 |
5310 |
Lake Elsinore |
33.7 |
1233 |
117.3 |
105 |
70 |
101 |
69 |
100 |
69 |
97 |
68 |
74 |
72 |
39 |
22 |
27 |
30 |
827 |
Lake Los Angeles |
34.7 |
2300 |
117.8 |
106 |
68 |
102 |
67 |
101 |
67 |
98 |
66 |
72 |
70 |
35 |
12 |
17 |
20 |
1455 |
Lake Spaulding |
39.3 |
5156 |
120.6 |
89 |
58 |
86 |
57 |
85 |
57 |
83 |
55 |
62 |
60 |
34 |
3 |
11 |
16 |
6447 |
Lakeland Village |
33.6 |
1233 |
117.3 |
105 |
70 |
101 |
69 |
100 |
69 |
97 |
68 |
74 |
72 |
39 |
12 |
27 |
30 |
827 |
Lakeport |
39 |
1347 |
122.9 |
97 |
67 |
93 |
66 |
92 |
65 |
88 |
63 |
69 |
67 |
41 |
20 |
26 |
29 |
3728 |
Lakeshore |
40.9 |
1075 |
119.2 |
104 |
69 |
100 |
68 |
99 |
68 |
95 |
66 |
71 |
69 |
28 |
29 |
34 |
36 |
- |
Lakeside |
32.8 |
690 |
117 |
95 |
69 |
90 |
68 |
89 |
68 |
86 |
66 |
72 |
70 |
20 |
26 |
31 |
34 |
- |
Lakewood |
33.9 |
45 |
118 |
98 |
70 |
90 |
68 |
88 |
68 |
84 |
66 |
72 |
70 |
22 |
33 |
37 |
40 |
- |
Lamont |
35.3 |
500 |
120 |
106 |
72 |
102 |
71 |
101 |
71 |
98 |
69 |
75 |
73 |
34 |
26 |
32 |
35 |
- |
Lancaster |
34.7 |
2340 |
118.2 |
106 |
68 |
102 |
67 |
101 |
67 |
98 |
66 |
72 |
70 |
35 |
12 |
17 |
20 |
- |
Larksfield-Wikiup |
38.5 |
170 |
122.8 |
99 |
69 |
96 |
68 |
95 |
68 |
92 |
66 |
71 |
69 |
35 |
24 |
27 |
29 |
1249 |
Larkspur |
37.9 |
20 |
122.5 |
97 |
68 |
91 |
66 |
89 |
66 |
84 |
64 |
69 |
68 |
34 |
28 |
33 |
35 |
- |
Las Plumas |
39.7 |
506 |
121.4 |
104 |
71 |
101 |
70 |
100 |
70 |
96 |
68 |
73 |
71 |
32 |
24 |
29 |
32 |
- |
Lathrop |
37.8 |
22 |
121.3 |
103 |
71 |
98 |
69 |
97 |
69 |
93 |
67 |
73 |
71 |
35 |
24 |
28 |
30 |
1300 |
Lava Beds |
41.7 |
4770 |
121.5 |
93 |
59 |
89 |
58 |
88 |
58 |
84 |
56 |
63 |
61 |
41 |
-1 |
4 |
11 |
- |
Lawndale |
33.9 |
66 |
118 |
92 |
69 |
85 |
68 |
84 |
68 |
80 |
66 |
71 |
69 |
16 |
37 |
40 |
42 |
- |
Le Grand |
37.2 |
255 |
120.3 |
101 |
70 |
96 |
68 |
95 |
68 |
91 |
66 |
72 |
70 |
38 |
23 |
28 |
31 |
2696 |
Lemon Grove |
32.7 |
437 |
117.2 |
96 |
71 |
88 |
69 |
87 |
69 |
84 |
67 |
72 |
70 |
19 |
34 |
38 |
41 |
- |
Lemoncove |
36.4 |
513 |
119 |
105 |
72 |
102 |
70 |
101 |
70 |
98 |
68 |
72 |
70 |
38 |
25 |
38 |
41 |
2513 |
Lemoore NAS |
36.3 |
228 |
120 |
104 |
72 |
101 |
71 |
100 |
71 |
97 |
69 |
74 |
72 |
37 |
19 |
25 |
28 |
2960 |
Lennox |
33.9 |
71 |
117.8 |
92 |
69 |
85 |
68 |
84 |
68 |
80 |
66 |
71 |
69 |
16 |
37 |
41 |
44 |
- |
Lincoln Village |
38 |
12 |
121.3 |
101 |
70 |
96 |
68 |
95 |
68 |
91 |
67 |
72 |
70 |
37 |
24 |
28 |
30 |
1334 |
Linda |
39 |
60 |
121.6 |
105 |
72 |
102 |
70 |
101 |
70 |
97 |
68 |
74 |
72 |
30 |
27 |
32 |
35 |
1160 |
Lindsay |
36.2 |
395 |
119.1 |
105 |
72 |
101 |
71 |
100 |
71 |
97 |
69 |
74 |
72 |
40 |
24 |
29 |
32 |
2634 |
Little Panoche |
36.8 |
677 |
120.7 |
100 |
68 |
94 |
67 |
92 |
67 |
86 |
66 |
71 |
69 |
33 |
23 |
28 |
31 |
- |
Live Oak |
39.2 |
75 |
121.7 |
105 |
70 |
102 |
69 |
101 |
69 |
97 |
69 |
73 |
71 |
36 |
24 |
29 |
32 |
1160 |
Livermore |
37.7 |
490 |
122 |
100 |
69 |
95 |
68 |
93 |
68 |
88 |
67 |
71 |
70 |
35 |
22 |
25 |
28 |
3012 |
Livingston |
37.3 |
165 |
120.7 |
103 |
72 |
100 |
70 |
99 |
70 |
95 |
68 |
74 |
72 |
39 |
24 |
30 |
34 |
1244 |
Llano Shawnee |
34.5 |
3820 |
117.8 |
104 |
68 |
99 |
67 |
98 |
67 |
95 |
65 |
71 |
69 |
31 |
21 |
27 |
31 |
- |
Lodgepole |
36.6 |
6735 |
118.7 |
84 |
57 |
80 |
56 |
80 |
56 |
78 |
54 |
60 |
58 |
26 |
-4 |
1 |
7 |
- |
Lodi |
38.1 |
40 |
121.3 |
101 |
70 |
97 |
68 |
95 |
68 |
91 |
67 |
72 |
70 |
38 |
23 |
28 |
31 |
2859 |
Loma Linda |
34 |
1150 |
117.5 |
106 |
70 |
103 |
69 |
102 |
69 |
99 |
67 |
74 |
72 |
36 |
27 |
32 |
35 |
- |
Lomita |
33.8 |
56 |
119 |
95 |
69 |
87 |
68 |
85 |
68 |
81 |
66 |
71 |
69 |
18 |
33 |
38 |
40 |
- |
Lompoc |
34.9 |
95 |
120.5 |
84 |
63 |
77 |
62 |
76 |
62 |
72 |
60 |
65 |
63 |
18 |
26 |
31 |
34 |
2888 |
Long Beach |
33.7 |
34 |
118.2 |
97 |
70 |
88 |
68 |
86 |
67 |
82 |
65 |
65 |
63 |
18 |
35 |
31 |
34 |
- |
Long Beach AP |
33.8 |
25 |
118.2 |
99 |
71 |
90 |
69 |
88 |
68 |
84 |
66 |
73 |
71 |
21 |
33 |
38 |
41 |
1606 |
Loomis |
38.8 |
408 |
121.2 |
107 |
71 |
103 |
70 |
102 |
70 |
98 |
69 |
74 |
72 |
39 |
21 |
27 |
30 |
- |
Los Alamitos NAS |
33.8 |
30 |
118.1 |
98 |
71 |
89 |
69 |
87 |
69 |
83 |
68 |
73 |
71 |
23 |
32 |
37 |
39 |
1740 |
Los Altos |
37.3 |
163 |
122 |
96 |
68 |
88 |
65 |
86 |
64 |
80 |
62 |
70 |
68 |
26 |
28 |
33 |
35 |
- |
Los Altos Hills |
37.3 |
183 |
122.1 |
93 |
67 |
85 |
64 |
83 |
64 |
77 |
63 |
68 |
66 |
25 |
28 |
33 |
35 |
1103 |
Los Angeles AP |
33.9 |
97 |
118.4 |
91 |
67 |
84 |
67 |
83 |
67 |
79 |
66 |
71 |
69 |
14 |
37 |
40 |
42 |
1819 |
Los Angeles CO |
34 |
270 |
118.2 |
99 |
69 |
92 |
68 |
90 |
68 |
86 |
67 |
72 |
70 |
21 |
38 |
41 |
43 |
1245 |
Los Banos |
37 |
120 |
120.9 |
100 |
70 |
96 |
68 |
94 |
68 |
88 |
67 |
72 |
70 |
42 |
22 |
28 |
31 |
2616 |
Los Banos Res |
37 |
407 |
120.9 |
101 |
70 |
97 |
68 |
95 |
68 |
89 |
67 |
72 |
70 |
42 |
23 |
29 |
31 |
- |
Los Gatos |
37.2 |
365 |
122 |
98 |
69 |
90 |
67 |
88 |
67 |
82 |
66 |
71 |
69 |
32 |
26 |
31 |
34 |
2741 |
Los Serranos |
34.1 |
714 |
117.7 |
104 |
70 |
100 |
69 |
98 |
69 |
94 |
68 |
74 |
72 |
35 |
27 |
32 |
35 |
706 |
Lucas Vly-Marinwood |
38.3 |
20 |
122.6 |
79 |
63 |
74 |
62 |
71 |
61 |
65 |
59 |
64 |
62 |
12 |
30 |
35 |
37 |
874 |
Lucerne Valley |
34.5 |
2957 |
117 |
105 |
67 |
101 |
66 |
100 |
66 |
98 |
64 |
71 |
69 |
38 |
12 |
19 |
24 |
- |
Lynwood |
33.9 |
88 |
118 |
98 |
70 |
90 |
69 |
88 |
69 |
83 |
67 |
72 |
70 |
21 |
32 |
37 |
39 |
- |
Madera |
37 |
268 |
120.1 |
105 |
72 |
101 |
70 |
100 |
70 |
96 |
68 |
74 |
72 |
40 |
24 |
29 |
32 |
2673 |
Madera Acres |
36.9 |
275 |
120.1 |
105 |
72 |
101 |
70 |
100 |
70 |
96 |
68 |
74 |
72 |
40 |
24 |
29 |
32 |
1250 |
Manhattan Beach |
33.9 |
120 |
118 |
91 |
69 |
84 |
68 |
83 |
68 |
79 |
66 |
71 |
69 |
12 |
38 |
42 |
45 |
- |
Manteca |
37.8 |
34 |
121.2 |
102 |
70 |
97 |
68 |
95 |
68 |
91 |
67 |
72 |
70 |
37 |
24 |
29 |
32 |
- |
Manzanita Lake |
40.5 |
5850 |
121.6 |
87 |
58 |
84 |
57 |
83 |
57 |
79 |
55 |
61 |
59 |
34 |
-3 |
2 |
8 |
7617 |
March AFB |
33.9 |
1511 |
117.3 |
103 |
70 |
99 |
68 |
98 |
67 |
94 |
65 |
74 |
71 |
34 |
23 |
30 |
33 |
2089 |
Maricopa |
35.1 |
675 |
119.4 |
106 |
71 |
102 |
70 |
101 |
70 |
98 |
68 |
74 |
72 |
29 |
25 |
30 |
33 |
2302 |
Marina |
36.7 |
20 |
121.8 |
86 |
66 |
77 |
63 |
75 |
63 |
70 |
61 |
67 |
64 |
18 |
32 |
37 |
40 |
- |
Marina del Rey |
34.1 |
40 |
118.5 |
91 |
69 |
84 |
68 |
83 |
68 |
79 |
66 |
71 |
69 |
12 |
38 |
42 |
45 |
383 |
Markley Cove |
38.5 |
480 |
122.1 |
104 |
70 |
99 |
69 |
97 |
69 |
93 |
67 |
72 |
70 |
39 |
23 |
29 |
31 |
- |
Martinez FS |
38 |
40 |
122.1 |
99 |
67 |
94 |
66 |
92 |
66 |
88 |
65 |
71 |
69 |
36 |
28 |
33 |
35 |
- |
Marysville |
39.2 |
60 |
121.6 |
105 |
72 |
102 |
70 |
101 |
70 |
97 |
68 |
74 |
72 |
36 |
27 |
32 |
35 |
2552 |
Mather AFB |
38.6 |
96 |
121.3 |
104 |
71 |
100 |
70 |
98 |
70 |
94 |
68 |
73 |
71 |
35 |
28 |
33 |
35 |
- |
Maywood |
34 |
170 |
118 |
97 |
70 |
91 |
69 |
89 |
69 |
85 |
67 |
72 |
70 |
21 |
34 |
38 |
41 |
- |
McClellan AFB |
38.7 |
86 |
121.4 |
105 |
71 |
102 |
70 |
100 |
70 |
96 |
68 |
74 |
71 |
35 |
23 |
28 |
21 |
2566 |
McCloud |
41.3 |
3300 |
122.1 |
96 |
63 |
93 |
62 |
91 |
62 |
87 |
60 |
66 |
64 |
42 |
5 |
13 |
18 |
5990 |
McFarland |
35.6 |
350 |
119.2 |
106 |
71 |
102 |
70 |
101 |
70 |
98 |
69 |
74 |
72 |
36 |
22 |
25 |
28 |
1162 |
McKinleyville |
40.9 |
33 |
124.1 |
75 |
61 |
69 |
59 |
68 |
59 |
65 |
58 |
61 |
60 |
11 |
28 |
31 |
33 |
1995 |
Mecca FS |
33.6 |
-180 |
116.1 |
115 |
75 |
111 |
75 |
110 |
75 |
107 |
74 |
81 |
79 |
30 |
24 |
29 |
32 |
1185 |
Mendota |
36.7 |
169 |
120.4 |
105 |
73 |
101 |
71 |
100 |
70 |
97 |
68 |
75 |
73 |
34 |
24 |
28 |
30 |
1273 |
Menlo Park |
37.4 |
65 |
122.3 |
94 |
67 |
86 |
65 |
84 |
65 |
78 |
63 |
69 |
67 |
25 |
27 |
32 |
34 |
- |
Mentone |
34.1 |
1700 |
117.1 |
106 |
70 |
102 |
69 |
101 |
69 |
98 |
67 |
74 |
72 |
34 |
27 |
32 |
35 |
741 |
Merced AP |
37.3 |
153 |
120.6 |
103 |
71 |
100 |
69 |
99 |
69 |
95 |
67 |
73 |
71 |
36 |
21 |
27 |
30 |
2653 |
Mill Creek |
35.1 |
2940 |
117 |
102 |
67 |
97 |
66 |
96 |
66 |
94 |
65 |
70 |
68 |
28 |
28 |
33 |
36 |
- |
Mill Valley |
37.9 |
80 |
122.6 |
97 |
68 |
91 |
66 |
89 |
66 |
84 |
64 |
70 |
68 |
28 |
28 |
33 |
35 |
3400 |
Millbrae |
37.6 |
10 |
122.4 |
90 |
66 |
82 |
63 |
80 |
63 |
74 |
61 |
67 |
65 |
24 |
30 |
35 |
37 |
- |
Milpitas |
37.4 |
15 |
121.9 |
94 |
68 |
87 |
65 |
85 |
65 |
79 |
63 |
70 |
67 |
27 |
27 |
32 |
35 |
- |
Mineral |
40.4 |
4911 |
121.6 |
90 |
60 |
87 |
59 |
86 |
59 |
82 |
57 |
63 |
61 |
38 |
2 |
7 |
14 |
7257 |
Mira Loma |
34 |
700 |
117.5 |
105 |
70 |
101 |
69 |
99 |
68 |
95 |
66 |
74 |
72 |
34 |
25 |
33 |
36 |
600 |
Miramar AFS |
32.9 |
477 |
117.1 |
97 |
69 |
91 |
68 |
90 |
68 |
86 |
67 |
72 |
70 |
22 |
32 |
36 |
38 |
1532 |
Miramonte |
34.4 |
750 |
119.1 |
102 |
71 |
97 |
69 |
95 |
69 |
91 |
68 |
73 |
71 |
38 |
25 |
29 |
32 |
771 |
Mission Viejo |
33.6 |
350 |
118 |
95 |
67 |
87 |
66 |
85 |
65 |
81 |
63 |
71 |
67 |
22 |
33 |
37 |
40 |
- |
Mitchell Caverns |
34.9 |
4350 |
117.0 |
102 |
64 |
98 |
63 |
97 |
63 |
94 |
61 |
69 |
67 |
29 |
21 |
27 |
30 |
- |
Modesto |
37.6 |
91 |
121 |
102 |
73 |
99 |
70 |
98 |
70 |
95 |
68 |
75 |
72 |
36 |
25 |
30 |
33 |
2671 |
Moffett Field NAS |
37.4 |
39 |
122.1 |
89 |
68 |
84 |
66 |
82 |
66 |
78 |
64 |
70 |
68 |
23 |
30 |
34 |
36 |
2511 |
Mojave |
35.1 |
2735 |
118.2 |
106 |
68 |
102 |
67 |
101 |
67 |
98 |
66 |
71 |
69 |
35 |
16 |
22 |
26 |
3012 |
Mono Lake |
38 |
6450 |
119.2 |
91 |
58 |
88 |
57 |
87 |
57 |
84 |
55 |
62 |
60 |
32 |
4 |
12 |
17 |
6518 |
Monrovia |
34.2 |
562 |
118.3 |
100 |
69 |
96 |
68 |
94 |
68 |
90 |
67 |
73 |
71 |
30 |
33 |
38 |
41 |
- |
Montague |
41.8 |
2648 |
122.5 |
99 |
66 |
95 |
65 |
94 |
65 |
90 |
63 |
69 |
67 |
39 |
3 |
11 |
16 |
5474 |
Montclair |
34 |
1220 |
117 |
104 |
69 |
100 |
68 |
98 |
68 |
94 |
66 |
73 |
71 |
35 |
28 |
33 |
35 |
- |
Montebello |
34 |
205 |
118.1 |
98 |
69 |
93 |
68 |
91 |
68 |
86 |
67 |
72 |
70 |
24 |
33 |
37 |
39 |
- |
Monterey AP |
36.6 |
245 |
121.9 |
86 |
65 |
77 |
62 |
75 |
62 |
70 |
61 |
66 |
63 |
20 |
30 |
35 |
38 |
3556 |
Monterey CO |
36.6 |
345 |
121.9 |
87 |
65 |
78 |
62 |
76 |
62 |
71 |
61 |
66 |
63 |
20 |
32 |
37 |
40 |
3169 |
Monterey Park |
34 |
380 |
118 |
99 |
69 |
94 |
68 |
92 |
68 |
87 |
67 |
72 |
70 |
23 |
30 |
35 |
37 |
- |
Monticello Dam |
38.5 |
505 |
122.1 |
105 |
71 |
100 |
70 |
98 |
70 |
94 |
68 |
73 |
71 |
39 |
26 |
31 |
34 |
- |
Moraga |
37.8 |
600 |
122.2 |
99 |
68 |
93 |
66 |
91 |
66 |
86 |
64 |
70 |
68 |
27 |
21 |
26 |
29 |
|
Moreno Valley |
33.9 |
1600 |
117.2 |
103 |
70 |
99 |
68 |
98 |
67 |
94 |
65 |
74 |
71 |
34 |
27 |
30 |
33 |
611 |
Morgan Hill |
37.1 |
350 |
120 |
100 |
69 |
92 |
68 |
90 |
68 |
85 |
66 |
71 |
69 |
25 |
26 |
31 |
34 |
- |
Morro Bay FD |
35.4 |
115 |
120.9 |
88 |
65 |
82 |
64 |
80 |
64 |
76 |
62 |
67 |
65 |
14 |
31 |
36 |
38 |
- |
Mount Baldy Notch |
34.3 |
7735 |
117.6 |
80 |
58 |
76 |
57 |
75 |
56 |
71 |
54 |
61 |
59 |
32 |
4 |
10 |
14 |
- |
Mount Diablo |
37.9 |
2100 |
121.9 |
101 |
68 |
96 |
66 |
93 |
66 |
87 |
65 |
68 |
59 |
28 |
27 |
32 |
35 |
4600 |
Mount Hamilton |
37.3 |
4206 |
121.7 |
95 |
59 |
88 |
58 |
86 |
58 |
81 |
56 |
63 |
61 |
18 |
18 |
24 |
27 |
4724 |
Mount Hebron RS |
41.8 |
4250 |
122 |
92 |
60 |
88 |
59 |
86 |
59 |
82 |
57 |
63 |
61 |
42 |
-10 |
-4 |
0 |
- |
Mount San Jacinto |
33.8 |
8417 |
116.6 |
82 |
56 |
77 |
55 |
76 |
55 |
73 |
53 |
61 |
59 |
35 |
-1 |
4 |
11 |
- |
Mount Shasta |
41.3 |
3535 |
122.3 |
93 |
62 |
89 |
61 |
88 |
61 |
84 |
59 |
65 |
63 |
34 |
8 |
15 |
20 |
5890 |
Mount Wilson |
34.2 |
5709 |
118.1 |
90 |
63 |
85 |
61 |
83 |
60 |
79 |
58 |
66 |
64 |
21 |
15 |
22 |
26 |
4296 |
Mountain Pass |
35.5 |
4730 |
115.5 |
100 |
65 |
96 |
64 |
95 |
64 |
92 |
63 |
68 |
66 |
29 |
11 |
18 |
23 |
- |
Mountain View |
37.5 |
95 |
121.9 |
93 |
67 |
85 |
64 |
83 |
64 |
77 |
62 |
68 |
66 |
25 |
28 |
33 |
35 |
- |
Muscoy |
34.2 |
1400 |
117.3 |
105 |
71 |
101 |
69 |
100 |
68 |
96 |
66 |
75 |
72 |
37 |
26 |
31 |
34 |
614 |
Nacimiento Dam |
35.8 |
770 |
120.9 |
100 |
68 |
94 |
66 |
92 |
66 |
88 |
64 |
70 |
68 |
35 |
22 |
28 |
31 |
- |
Napa State Hospital |
37.3 |
60 |
122.3 |
94 |
67 |
91 |
67 |
90 |
67 |
86 |
66 |
71 |
70 |
29 |
26 |
31 |
34 |
2749 |
National City |
32.7 |
34 |
117 |
87 |
70 |
82 |
68 |
81 |
68 |
78 |
66 |
71 |
69 |
10 |
36 |
40 |
42 |
- |
Needles AP |
34.8 |
913 |
114.6 |
117 |
73 |
114 |
72 |
113 |
72 |
110 |
71 |
77 |
75 |
26 |
27 |
32 |
35 |
1391 |
Nevada City |
39.3 |
2600 |
121 |
97 |
66 |
94 |
64 |
92 |
64 |
88 |
63 |
68 |
66 |
41 |
14 |
21 |
25 |
4900 |
Newark |
37.5 |
10 |
122 |
94 |
68 |
89 |
67 |
87 |
67 |
82 |
65 |
70 |
68 |
24 |
29 |
34 |
36 |
- |
Newhall Soledad |
34.4 |
1243 |
118.6 |
104 |
70 |
100 |
68 |
99 |
68 |
95 |
67 |
73 |
71 |
42 |
27 |
33 |
36 |
- |
Newman |
37.3 |
90 |
121.1 |
104 |
71 |
99 |
69 |
97 |
69 |
93 |
67 |
73 |
71 |
38 |
22 |
28 |
31 |
- |
Newport Beach |
33.6 |
10 |
117.9 |
87 |
68 |
80 |
66 |
78 |
66 |
72 |
65 |
70 |
68 |
12 |
34 |
39 |
41 |
1952 |
Nipomo |
35 |
330 |
120.5 |
90 |
66 |
83 |
64 |
82 |
63 |
78 |
61 |
67 |
65 |
23 |
25 |
31 |
33 |
1035 |
Norco |
33.9 |
700 |
117 |
103 |
70 |
99 |
69 |
98 |
69 |
94 |
67 |
74 |
72 |
34 |
27 |
32 |
35 |
- |
North Auburn |
38.9 |
1300 |
121.1 |
103 |
69 |
100 |
67 |
99 |
67 |
95 |
66 |
72 |
69 |
33 |
25 |
30 |
33 |
1518 |
North Fork RS |
37.2 |
2630 |
119.5 |
98 |
66 |
95 |
65 |
94 |
64 |
92 |
62 |
69 |
67 |
36 |
15 |
22 |
26 |
- |
North Highlands |
38.6 |
45 |
121.4 |
104 |
71 |
100 |
69 |
98 |
69 |
94 |
67 |
73 |
71 |
35 |
23 |
28 |
31 |
2566 |
North Hollywood |
34.2 |
619 |
118.4 |
102 |
70 |
97 |
69 |
95 |
69 |
91 |
67 |
73 |
71 |
31 |
28 |
33 |
36 |
- |
Northridge |
34.2 |
875 |
118.5 |
101 |
70 |
96 |
69 |
94 |
69 |
90 |
67 |
73 |
71 |
36 |
30 |
35 |
38 |
650 |
Norwalk |
33.9 |
97 |
118.1 |
99 |
69 |
90 |
68 |
88 |
68 |
84 |
67 |
72 |
70 |
26 |
31 |
35 |
37 |
- |
Novato |
38.1 |
370 |
122.5 |
94 |
64 |
87 |
63 |
85 |
63 |
80 |
61 |
68 |
66 |
30 |
25 |
30 |
32 |
- |
Oakdale |
37.8 |
215 |
120.9 |
102 |
71 |
99 |
69 |
97 |
69 |
93 |
67 |
73 |
71 |
37 |
22 |
28 |
32 |
- |
Oakland AP |
37.7 |
6 |
122.2 |
91 |
66 |
84 |
64 |
82 |
64 |
77 |
62 |
67 |
65 |
20 |
32 |
34 |
37 |
2909 |
Oakland Museum |
37.8 |
30 |
122.2 |
96 |
68 |
89 |
66 |
87 |
65 |
82 |
63 |
69 |
67 |
20 |
31 |
33 |
36 |
- |
Oakley |
38 |
20 |
121.7 |
102 |
70 |
97 |
68 |
95 |
68 |
91 |
66 |
70 |
69 |
34 |
22 |
28 |
31 |
- |
Oceano |
35.1 |
20 |
120.6 |
93 |
69 |
86 |
64 |
84 |
64 |
80 |
62 |
67 |
65 |
18 |
30 |
34 |
37 |
795 |
Oceanside |
33.2 |
10 |
117.4 |
84 |
69 |
80 |
67 |
78 |
67 |
74 |
65 |
70 |
68 |
10 |
33 |
37 |
39 |
- |
Oildale |
35.5 |
450 |
119 |
106 |
71 |
102 |
70 |
101 |
70 |
98 |
68 |
74 |
72 |
34 |
26 |
31 |
35 |
- |
Ojai |
34.5 |
750 |
119.3 |
102 |
71 |
97 |
69 |
95 |
69 |
91 |
68 |
73 |
71 |
38 |
25 |
29 |
32 |
2145 |
Olivehurst |
39 |
64 |
121.6 |
105 |
72 |
102 |
70 |
101 |
70 |
97 |
68 |
74 |
72 |
36 |
27 |
32 |
35 |
1160 |
Ontario AP |
34 |
934 |
117 |
105 |
70 |
101 |
69 |
99 |
68 |
95 |
66 |
74 |
72 |
34 |
26 |
33 |
36 |
1710 |
Opal Cliffs |
37 |
125 |
122 |
94 |
68 |
88 |
66 |
86 |
66 |
81 |
64 |
69 |
67 |
28 |
27 |
32 |
35 |
1097 |
Orange |
33.6 |
194 |
118 |
99 |
70 |
92 |
68 |
90 |
68 |
85 |
67 |
72 |
70 |
27 |
33 |
37 |
40 |
- |
Orange Cove |
36.6 |
431 |
119.3 |
104 |
71 |
100 |
69 |
99 |
69 |
97 |
68 |
73 |
71 |
38 |
25 |
30 |
33 |
2684 |
Orangevale |
38.7 |
140 |
121.2 |
105 |
72 |
102 |
70 |
100 |
70 |
96 |
68 |
74 |
71 |
36 |
24 |
30 |
34 |
- |
Orick Prairie Creek |
41.4 |
161 |
124 |
80 |
61 |
75 |
60 |
74 |
60 |
70 |
59 |
63 |
61 |
23 |
25 |
30 |
33 |
4816 |
Orinda |
37.9 |
550 |
122.2 |
99 |
68 |
93 |
66 |
91 |
66 |
86 |
64 |
70 |
68 |
32 |
21 |
26 |
29 |
- |
Orland |
39.8 |
254 |
122.2 |
105 |
71 |
102 |
70 |
101 |
70 |
97 |
68 |
73 |
71 |
36 |
22 |
28 |
31 |
2824 |
Orleans |
41.3 |
403 |
123.5 |
104 |
70 |
97 |
68 |
95 |
68 |
91 |
66 |
71 |
69 |
42 |
21 |
27 |
30 |
3628 |
Orosi |
36.5 |
400 |
119.3 |
104 |
73 |
101 |
70 |
100 |
70 |
96 |
69 |
75 |
73 |
36 |
24 |
30 |
34 |
1130 |
Oroville East |
39.5 |
171 |
121.6 |
106 |
71 |
104 |
70 |
102 |
70 |
98 |
69 |
74 |
72 |
37 |
25 |
30 |
33 |
1385 |
Oroville RS |
39.5 |
300 |
121.6 |
106 |
71 |
104 |
70 |
102 |
70 |
98 |
69 |
74 |
72 |
37 |
25 |
30 |
33 |
- |
Otay-Castle Pk |
32.6 |
500 |
117 |
87 |
68 |
81 |
66 |
79 |
65 |
74 |
63 |
69 |
67 |
10 |
33 |
38 |
40 |
- |
Oxnard AFB |
34.2 |
49 |
119.2 |
94 |
69 |
86 |
68 |
84 |
68 |
79 |
67 |
71 |
69 |
21 |
30 |
34 |
37 |
2068 |
Pacific Grove |
36.7 |
114 |
122 |
87 |
66 |
78 |
63 |
76 |
63 |
71 |
61 |
67 |
64 |
19 |
31 |
35 |
37 |
- |
Pacifica |
37.6 |
13 |
122 |
87 |
65 |
79 |
62 |
77 |
62 |
71 |
60 |
66 |
64 |
16 |
31 |
35 |
37 |
- |
Pacoima |
34.3 |
895 |
118.4 |
104 |
71 |
99 |
70 |
98 |
70 |
94 |
68 |
74 |
72 |
35 |
29 |
34 |
37 |
664 |
Palermo |
39.4 |
154 |
121.5 |
106 |
71 |
104 |
70 |
102 |
70 |
98 |
69 |
74 |
72 |
37 |
25 |
30 |
33 |
1170 |
Palm Desert |
33.7 |
200 |
116.5 |
116 |
74 |
112 |
73 |
111 |
73 |
108 |
72 |
79 |
78 |
34 |
26 |
32 |
34 |
- |
Palm Desert Country |
33.7 |
243 |
116.3 |
116 |
74 |
112 |
73 |
111 |
73 |
108 |
72 |
79 |
78 |
34 |
26 |
32 |
34 |
374 |
Palm Springs |
33.8 |
411 |
116.5 |
117 |
74 |
113 |
73 |
112 |
73 |
109 |
72 |
79 |
78 |
35 |
26 |
31 |
34 |
1109 |
Palmdale AP |
34.6 |
2517 |
118.1 |
107 |
67 |
103 |
67 |
102 |
66 |
98 |
64 |
71 |
69 |
33 |
12 |
20 |
24 |
2929 |
Palmdale CO |
34.6 |
2596 |
118.1 |
106 |
67 |
102 |
67 |
101 |
66 |
97 |
64 |
71 |
69 |
35 |
13 |
21 |
25 |
2908 |
Palo Alto |
37.5 |
25 |
122.1 |
93 |
66 |
85 |
64 |
83 |
64 |
77 |
62 |
68 |
66 |
25 |
26 |
31 |
34 |
2891 |
Palomar Obsy |
33.4 |
5545 |
116.9 |
90 |
62 |
85 |
61 |
84 |
61 |
80 |
59 |
66 |
64 |
22 |
16 |
20 |
23 |
4141 |
Palos Verdes |
33.8 |
216 |
119 |
92 |
69 |
84 |
68 |
82 |
68 |
78 |
66 |
71 |
69 |
14 |
38 |
43 |
46 |
- |
Panorama City |
34.2 |
801 |
118.5 |
103 |
71 |
98 |
69 |
96 |
69 |
92 |
67 |
74 |
71 |
32 |
28 |
33 |
36 |
664 |
Paradise |
39.8 |
1750 |
121.6 |
102 |
69 |
99 |
67 |
98 |
67 |
94 |
66 |
71 |
69 |
34 |
25 |
30 |
33 |
- |
Paramount |
33.9 |
70 |
117 |
98 |
70 |
90 |
69 |
88 |
69 |
84 |
67 |
72 |
70 |
22 |
32 |
37 |
40 |
- |
Parker Res |
34.3 |
738 |
114.2 |
115 |
74 |
112 |
73 |
111 |
73 |
108 |
72 |
79 |
77 |
26 |
32 |
37 |
40 |
1223 |
Parkway-South Sacramento |
38.5 |
17 |
121.4 |
104 |
71 |
100 |
70 |
98 |
70 |
94 |
68 |
73 |
71 |
32 |
30 |
35 |
37 |
1150 |
Parlier |
36.6 |
320 |
119.5 |
104 |
73 |
101 |
71 |
100 |
70 |
97 |
68 |
75 |
73 |
38 |
24 |
30 |
34 |
1262 |
Pasadena |
34.2 |
864 |
118.2 |
99 |
69 |
94 |
68 |
92 |
68 |
88 |
67 |
73 |
71 |
30 |
32 |
37 |
40 |
1551 |
Paso Robles AP |
35.7 |
815 |
120.7 |
104 |
66 |
97 |
66 |
96 |
66 |
92 |
65 |
70 |
68 |
40 |
19 |
23 |
26 |
2973 |
Paso Robles CO |
35.6 |
700 |
120.7 |
102 |
65 |
95 |
65 |
94 |
65 |
90 |
65 |
69 |
67 |
44 |
16 |
20 |
23 |
2885 |
Patterson |
37.4 |
97 |
121.1 |
101 |
72 |
96 |
70 |
94 |
69 |
90 |
67 |
74 |
72 |
36 |
24 |
30 |
34 |
1240 |
Pedley |
34 |
718 |
117.5 |
105 |
70 |
101 |
69 |
99 |
68 |
95 |
66 |
74 |
72 |
34 |
26 |
33 |
36 |
600 |
Pendleton MCB |
33.3 |
63 |
117.3 |
92 |
68 |
87 |
67 |
85 |
67 |
81 |
66 |
71 |
69 |
22 |
34 |
39 |
41 |
1532 |
Pendleton MCB Coast |
33.2 |
24 |
117.4 |
84 |
69 |
80 |
67 |
79 |
67 |
75 |
65 |
70 |
68 |
10 |
39 |
44 |
46 |
1782 |
Perris |
33.8 |
1470 |
117.2 |
105 |
70 |
101 |
69 |
100 |
69 |
97 |
68 |
74 |
72 |
39 |
22 |
27 |
30 |
- |
Petaluma FS 2 |
38.2 |
16 |
122.6 |
98 |
69 |
92 |
67 |
90 |
67 |
85 |
66 |
72 |
69 |
31 |
24 |
29 |
32 |
2959 |
Pico Rivera |
34 |
180 |
118 |
98 |
70 |
91 |
69 |
89 |
69 |
85 |
67 |
72 |
70 |
24 |
31 |
35 |
38 |
- |
Piedmont |
37.8 |
325 |
122 |
96 |
68 |
89 |
66 |
87 |
65 |
82 |
63 |
70 |
68 |
23 |
31 |
33 |
36 |
- |
Pinnacles NM |
36.5 |
1307 |
121.2 |
98 |
68 |
94 |
67 |
93 |
66 |
89 |
64 |
70 |
68 |
45 |
20 |
26 |
29 |
2956 |
Pinole |
38 |
10 |
122.3 |
91 |
66 |
87 |
65 |
86 |
65 |
82 |
64 |
69 |
67 |
25 |
30 |
35 |
38 |
- |
Pismo Beach |
35.1 |
80 |
120.6 |
92 |
66 |
85 |
64 |
84 |
64 |
80 |
62 |
67 |
65 |
16 |
30 |
34 |
37 |
2756 |
Pittsburg |
38 |
50 |
121.8 |
102 |
70 |
97 |
68 |
95 |
68 |
90 |
67 |
72 |
70 |
34 |
26 |
32 |
35 |
- |
Placentia |
33.9 |
323 |
118 |
101 |
69 |
93 |
68 |
91 |
68 |
87 |
67 |
73 |
71 |
28 |
30 |
34 |
37 |
- |
Placerville |
38.7 |
1890 |
120.8 |
101 |
67 |
98 |
66 |
97 |
66 |
93 |
65 |
70 |
68 |
42 |
20 |
26 |
29 |
4086 |
Placerville IFG |
38.7 |
2755 |
120.8 |
100 |
66 |
97 |
65 |
96 |
65 |
92 |
64 |
69 |
67 |
42 |
23 |
28 |
31 |
- |
Platina |
40.4 |
2260 |
122.9 |
96 |
65 |
92 |
64 |
91 |
63 |
87 |
61 |
67 |
65 |
36 |
13 |
20 |
24 |
- |
Pleasant Hill |
37.9 |
102 |
122 |
96 |
68 |
93 |
67 |
92 |
67 |
88 |
65 |
70 |
68 |
34 |
25 |
30 |
33 |
- |
Pleasanton |
37.6 |
350 |
121.8 |
97 |
68 |
94 |
67 |
93 |
67 |
89 |
65 |
70 |
68 |
35 |
24 |
29 |
32 |
- |
Point Arena |
38.9 |
100 |
123.7 |
76 |
62 |
72 |
60 |
71 |
60 |
67 |
58 |
63 |
61 |
19 |
29 |
32 |
34 |
4747 |
Point Arguello |
34.6 |
76 |
120.7 |
75 |
64 |
71 |
63 |
69 |
62 |
65 |
59 |
65 |
63 |
17 |
29 |
32 |
35 |
3826 |
Point Mugu |
34.1 |
14 |
119.1 |
88 |
68 |
81 |
67 |
79 |
67 |
75 |
66 |
70 |
68 |
15 |
33 |
37 |
39 |
2328 |
Point Piedras Blancas |
35.7 |
59 |
121.3 |
73 |
60 |
67 |
59 |
65 |
59 |
61 |
57 |
62 |
60 |
10 |
36 |
41 |
43 |
3841 |
Pomona Cal Poly |
34.1 |
740 |
117.8 |
102 |
70 |
98 |
69 |
97 |
69 |
93 |
67 |
74 |
72 |
36 |
27 |
32 |
35 |
1971 |
Port Chicago ND |
38 |
50 |
122 |
98 |
69 |
94 |
68 |
92 |
68 |
88 |
66 |
71 |
69 |
34 |
28 |
33 |
36 |
- |
Port Hueneme |
34.2 |
13 |
119 |
88 |
68 |
81 |
67 |
79 |
67 |
75 |
66 |
70 |
68 |
15 |
33 |
37 |
39 |
2334 |
Porterville |
36.1 |
393 |
119 |
106 |
71 |
102 |
70 |
101 |
70 |
97 |
69 |
74 |
72 |
36 |
25 |
30 |
33 |
2456 |
Portola |
39.8 |
4850 |
120.5 |
92 |
63 |
89 |
61 |
88 |
61 |
84 |
59 |
65 |
63 |
48 |
-9 |
-3 |
1 |
7111 |
Posey 3 E |
35.8 |
4960 |
119 |
89 |
62 |
86 |
61 |
85 |
61 |
82 |
59 |
65 |
63 |
26 |
9 |
16 |
21 |
- |
Potter Valley PH |
39.4 |
1015 |
123.1 |
101 |
68 |
96 |
67 |
94 |
67 |
89 |
65 |
70 |
68 |
40 |
20 |
26 |
29 |
3276 |
Poway Valley |
33 |
500 |
117 |
100 |
70 |
94 |
69 |
93 |
69 |
89 |
68 |
73 |
71 |
26 |
29 |
33 |
35 |
- |
Priest Valley |
36.2 |
2300 |
120.7 |
97 |
66 |
93 |
65 |
92 |
65 |
88 |
63 |
69 |
67 |
34 |
13 |
20 |
24 |
4144 |
Prunedale |
36.6 |
260 |
121.7 |
86 |
66 |
83 |
65 |
82 |
64 |
79 |
62 |
68 |
66 |
20 |
26 |
31 |
34 |
1100 |
Quartz Hill |
34.6 |
2428 |
118.2 |
106 |
68 |
102 |
67 |
101 |
67 |
98 |
66 |
72 |
70 |
35 |
12 |
17 |
20 |
1455 |
Quincy |
39.9 |
3409 |
120.9 |
101 |
64 |
98 |
63 |
97 |
63 |
93 |
62 |
68 |
66 |
45 |
1 |
6 |
13 |
5763 |
Ramona Spaulding |
33.1 |
1480 |
116.8 |
103 |
70 |
97 |
69 |
96 |
69 |
92 |
68 |
73 |
71 |
40 |
22 |
28 |
31 |
- |
Rancho Bernardo |
33 |
500 |
117.1 |
96 |
69 |
91 |
68 |
89 |
68 |
85 |
67 |
72 |
70 |
26 |
29 |
34 |
36 |
- |
Rancho Cordova |
38.6 |
190 |
121.3 |
104 |
72 |
100 |
69 |
98 |
69 |
94 |
68 |
74 |
71 |
35 |
26 |
31 |
33 |
- |
Rancho Mirage |
33.8 |
248 |
116.4 |
117 |
74 |
113 |
73 |
112 |
73 |
109 |
72 |
79 |
78 |
33 |
26 |
31 |
34 |
374 |
Rancho Palos Verdes |
33.7 |
216 |
118.2 |
92 |
69 |
84 |
68 |
82 |
68 |
78 |
66 |
71 |
69 |
14 |
38 |
43 |
46 |
- |
Rancho San Diego |
32.8 |
300 |
117.0 |
94 |
69 |
86 |
68 |
85 |
68 |
82 |
66 |
71 |
69 |
30 |
34 |
38 |
41 |
404 |
Rancho Santa Margarita |
33.6 |
116 |
117.6 |
95 |
67 |
87 |
66 |
85 |
65 |
81 |
63 |
71 |
67 |
22 |
33 |
37 |
40 |
496 |
Randsburg |
35.3 |
3570 |
117.7 |
105 |
67 |
102 |
66 |
101 |
66 |
97 |
65 |
70 |
68 |
30 |
19 |
25 |
28 |
2922 |
Red Bluff AP |
40.2 |
342 |
122.3 |
107 |
70 |
104 |
69 |
102 |
68 |
98 |
66 |
73 |
71 |
31 |
24 |
29 |
31 |
2688 |
Redding FS 4 |
40.6 |
470 |
122.4 |
107 |
69 |
103 |
68 |
101 |
68 |
97 |
67 |
72 |
70 |
30 |
26 |
31 |
34 |
2544 |
Redlands |
34.1 |
1318 |
117.2 |
106 |
70 |
102 |
69 |
101 |
69 |
98 |
67 |
74 |
72 |
34 |
27 |
32 |
35 |
1993 |
Redondo Beach |
33.8 |
45 |
118.3 |
92 |
69 |
84 |
68 |
82 |
68 |
78 |
66 |
71 |
69 |
12 |
37 |
42 |
44 |
- |
Redwood City |
37.5 |
31 |
122.2 |
90 |
67 |
86 |
66 |
85 |
66 |
81 |
64 |
69 |
67 |
28 |
28 |
33 |
35 |
2599 |
Reedley |
36.6 |
344 |
119.7 |
104 |
71 |
101 |
70 |
100 |
70 |
96 |
68 |
74 |
72 |
40 |
24 |
30 |
34 |
- |
Reseda |
34.2 |
736 |
118.5 |
103 |
71 |
98 |
69 |
96 |
69 |
92 |
67 |
74 |
71 |
32 |
28 |
33 |
36 |
664 |
Rialto |
34.1 |
1254 |
117 |
105 |
70 |
101 |
69 |
100 |
68 |
96 |
66 |
74 |
72 |
35 |
28 |
33 |
35 |
- |
Richardson Grove |
40 |
500 |
123.8 |
96 |
67 |
92 |
66 |
91 |
66 |
87 |
64 |
69 |
67 |
28 |
25 |
30 |
33 |
- |
Richmond |
37.9 |
55 |
121.6 |
88 |
65 |
84 |
64 |
82 |
64 |
77 |
62 |
67 |
65 |
17 |
31 |
36 |
38 |
2684 |
Ridgecrest |
35.6 |
2340 |
117.8 |
110 |
70 |
106 |
68 |
105 |
68 |
102 |
66 |
75 |
71 |
35 |
15 |
22 |
26 |
- |
Rio Del Mar |
37 |
50 |
121.9 |
94 |
67 |
88 |
66 |
87 |
65 |
83 |
63 |
69 |
67 |
30 |
27 |
32 |
35 |
1097 |
Rio Linda |
38.6 |
86 |
121.5 |
104 |
72 |
100 |
70 |
98 |
70 |
94 |
68 |
74 |
71 |
32 |
28 |
33 |
35 |
1290 |
Ripon |
37.7 |
61 |
121.1 |
102 |
70 |
97 |
68 |
95 |
68 |
91 |
67 |
72 |
70 |
37 |
23 |
30 |
33 |
1240 |
Riverbank |
37.7 |
133 |
120.9 |
102 |
73 |
99 |
70 |
98 |
70 |
95 |
68 |
75 |
72 |
36 |
25 |
30 |
33 |
1240 |
Riverside Exp Sta |
34 |
986 |
117.4 |
106 |
71 |
102 |
69 |
101 |
69 |
97 |
67 |
75 |
72 |
36 |
29 |
34 |
36 |
- |
Riverside FS 3 |
34 |
840 |
117.4 |
104 |
70 |
100 |
69 |
99 |
68 |
95 |
65 |
74 |
72 |
37 |
27 |
32 |
35 |
1818 |
Rocklin |
38.8 |
239 |
121.2 |
108 |
72 |
104 |
70 |
103 |
70 |
99 |
69 |
74 |
72 |
39 |
20 |
26 |
29 |
3143 |
Rodeo |
38.1 |
15 |
122.3 |
93 |
67 |
90 |
66 |
88 |
66 |
84 |
64 |
70 |
68 |
23 |
28 |
33 |
36 |
823 |
Rohnert Park |
38.4 |
106 |
122.6 |
99 |
69 |
96 |
68 |
95 |
68 |
92 |
66 |
71 |
69 |
33 |
24 |
27 |
29 |
- |
Rolling Hills |
33.6 |
216 |
119 |
92 |
69 |
84 |
68 |
82 |
68 |
78 |
66 |
71 |
69 |
15 |
38 |
43 |
46 |
- |
Rosamond |
34.8 |
2326 |
118.2 |
106 |
68 |
102 |
67 |
101 |
67 |
98 |
66 |
71 |
69 |
35 |
16 |
22 |
26 |
1455 |
Roseland |
38.4 |
167 |
122.7 |
99 |
69 |
96 |
68 |
95 |
68 |
92 |
66 |
71 |
69 |
35 |
24 |
27 |
29 |
1249 |
Rosemead |
34 |
275 |
118 |
98 |
70 |
90 |
69 |
88 |
69 |
84 |
67 |
72 |
70 |
27 |
30 |
35 |
37 |
- |
Rosemont |
38.3 |
190 |
121.4 |
104 |
71 |
100 |
70 |
98 |
70 |
94 |
68 |
73 |
71 |
32 |
30 |
35 |
37 |
1025 |
Roseville |
38.7 |
160 |
121.2 |
105 |
71 |
102 |
70 |
100 |
70 |
96 |
68 |
74 |
71 |
36 |
24 |
30 |
34 |
- |
Rossmoor |
33.8 |
20 |
118.1 |
92 |
67 |
85 |
64 |
83 |
64 |
79 |
62 |
71 |
69 |
19 |
32 |
37 |
39 |
- |
Rowland Hts |
33.9 |
540 |
118 |
99 |
70 |
93 |
69 |
91 |
69 |
86 |
68 |
73 |
71 |
27 |
29 |
34 |
36 |
- |
Rubidoux |
34 |
792 |
117 |
106 |
71 |
102 |
70 |
101 |
70 |
97 |
68 |
75 |
73 |
36 |
27 |
32 |
35 |
- |
Sacramento AP |
38.5 |
17 |
121.5 |
104 |
72 |
100 |
70 |
98 |
70 |
94 |
68 |
74 |
71 |
35 |
26 |
31 |
33 |
2843 |
Sacramento CO |
38.6 |
84 |
121.5 |
104 |
71 |
100 |
70 |
98 |
70 |
94 |
68 |
73 |
71 |
32 |
30 |
35 |
37 |
- |
Saint Helena |
38.5 |
225 |
122.5 |
102 |
70 |
98 |
69 |
97 |
69 |
93 |
67 |
72 |
70 |
40 |
22 |
28 |
31 |
2878 |
Saint Mary's College |
37.8 |
623 |
122.1 |
98 |
69 |
93 |
68 |
91 |
68 |
86 |
66 |
71 |
69 |
28 |
21 |
27 |
30 |
3543 |
Salinas 3 E |
36.7 |
85 |
121.6 |
86 |
66 |
83 |
65 |
82 |
64 |
79 |
62 |
68 |
66 |
20 |
26 |
31 |
34 |
- |
Salinas AP |
36.7 |
69 |
121.6 |
85 |
67 |
82 |
65 |
81 |
64 |
78 |
62 |
69 |
66 |
20 |
28 |
33 |
35 |
2959 |
Salt Springs PH |
38.5 |
3700 |
120.2 |
95 |
62 |
92 |
61 |
91 |
61 |
87 |
59 |
66 |
64 |
27 |
19 |
25 |
28 |
3857 |
Salyer RS |
40.9 |
623 |
123.6 |
102 |
69 |
95 |
67 |
93 |
66 |
87 |
64 |
70 |
68 |
33 |
22 |
28 |
31 |
- |
San Anselmo |
38 |
50 |
122 |
95 |
67 |
89 |
66 |
87 |
66 |
82 |
65 |
70 |
68 |
32 |
26 |
31 |
33 |
- |
San Antonio Canyon |
34.2 |
2394 |
117.7 |
100 |
68 |
96 |
67 |
94 |
67 |
90 |
65 |
72 |
70 |
33 |
29 |
35 |
39 |
- |
San Antonio Mission |
36 |
1060 |
117.7 |
99 |
69 |
94 |
68 |
92 |
68 |
88 |
67 |
71 |
69 |
28 |
19 |
25 |
28 |
- |
San Bernardino |
34.1 |
1125 |
117.3 |
106 |
70 |
102 |
69 |
101 |
69 |
98 |
68 |
75 |
72 |
39 |
27 |
31 |
33 |
1777 |
San Bruno |
37.7 |
20 |
122.4 |
86 |
66 |
80 |
64 |
78 |
64 |
73 |
62 |
67 |
65 |
23 |
30 |
35 |
38 |
3042 |
San Carlos |
37.5 |
26 |
122.3 |
92 |
67 |
88 |
65 |
86 |
65 |
82 |
63 |
68 |
66 |
28 |
28 |
33 |
35 |
- |
San Clemente |
33.4 |
208 |
118.6 |
91 |
68 |
85 |
67 |
84 |
67 |
80 |
66 |
71 |
69 |
12 |
31 |
35 |
37 |
- |
San Diego AP |
32.7 |
13 |
117.2 |
88 |
70 |
83 |
69 |
82 |
69 |
78 |
68 |
72 |
70 |
13 |
38 |
42 |
44 |
1507 |
San Dimas |
34 |
955 |
118.4 |
102 |
70 |
98 |
69 |
96 |
69 |
92 |
67 |
74 |
72 |
35 |
30 |
35 |
37 |
- |
San Fernando |
34.3 |
977 |
118.5 |
104 |
71 |
99 |
70 |
98 |
70 |
94 |
68 |
74 |
72 |
37 |
30 |
35 |
37 |
1800 |
San Francisco AP |
37.6 |
8 |
122.4 |
89 |
66 |
83 |
64 |
80 |
63 |
74 |
61 |
67 |
64 |
20 |
31 |
35 |
38 |
3042 |
San Francisco CO |
37.8 |
52 |
122.4 |
84 |
65 |
79 |
63 |
77 |
62 |
71 |
60 |
66 |
63 |
14 |
38 |
41 |
44 |
3080 |
San Gabriel FD |
34.1 |
450 |
118.1 |
99 |
70 |
94 |
69 |
92 |
69 |
88 |
68 |
73 |
71 |
30 |
30 |
35 |
37 |
1532 |
San Gregorio 2 SE |
37.3 |
275 |
122.4 |
87 |
66 |
81 |
63 |
79 |
63 |
74 |
61 |
68 |
65 |
30 |
27 |
32 |
35 |
- |
San Jacinto |
33.8 |
1535 |
117 |
110 |
70 |
105 |
69 |
104 |
69 |
102 |
68 |
75 |
73 |
41 |
20 |
26 |
29 |
2376 |
San Jose |
37.4 |
67 |
121.9 |
94 |
68 |
86 |
66 |
84 |
66 |
78 |
64 |
70 |
68 |
26 |
29 |
34 |
36 |
2438 |
San Leandro |
37.7 |
45 |
122.2 |
89 |
67 |
83 |
64 |
81 |
64 |
76 |
62 |
69 |
66 |
22 |
28 |
33 |
35 |
- |
San Lorenzo |
37.7 |
45 |
122.1 |
89 |
67 |
83 |
64 |
81 |
64 |
76 |
62 |
69 |
66 |
23 |
28 |
33 |
36 |
- |
San Luis Dam |
37.1 |
277 |
121.1 |
97 |
68 |
91 |
66 |
90 |
66 |
86 |
64 |
70 |
68 |
32 |
25 |
30 |
33 |
- |
San Luis Obispo |
35.3 |
320 |
120.7 |
94 |
63 |
87 |
63 |
85 |
63 |
81 |
62 |
67 |
65 |
26 |
30 |
33 |
35 |
2498 |
San Marcos |
33.1 |
567 |
117.2 |
97 |
69 |
98 |
68 |
94 |
68 |
84 |
67 |
72 |
70 |
29 |
26 |
31 |
34 |
662 |
San Marino |
34.2 |
300 |
118.1 |
100 |
69 |
95 |
68 |
93 |
68 |
88 |
66 |
73 |
71 |
28 |
30 |
35 |
37 |
- |
San Mateo |
37.5 |
21 |
122.3 |
92 |
67 |
84 |
65 |
82 |
65 |
76 |
63 |
68 |
66 |
24 |
31 |
36 |
38 |
2655 |
San Nicholas Island |
33.2 |
504 |
119.5 |
85 |
66 |
78 |
65 |
76 |
65 |
70 |
64 |
69 |
67 |
11 |
39 |
43 |
45 |
2454 |
San Pablo |
37.6 |
30 |
122.3 |
90 |
65 |
84 |
63 |
82 |
63 |
77 |
61 |
69 |
66 |
17 |
29 |
34 |
37 |
- |
San Pedro |
33.7 |
10 |
118.3 |
92 |
69 |
84 |
68 |
82 |
68 |
78 |
66 |
72 |
70 |
13 |
35 |
31 |
34 |
1819 |
San Rafael |
38 |
40 |
122.6 |
96 |
67 |
90 |
65 |
88 |
65 |
83 |
63 |
71 |
68 |
29 |
30 |
35 |
37 |
2440 |
San Ramon |
37.7 |
360 |
122 |
99 |
69 |
93 |
67 |
91 |
67 |
86 |
65 |
70 |
68 |
35 |
24 |
29 |
32 |
1369 |
Sandberg |
34.8 |
4517 |
118.7 |
95 |
63 |
91 |
61 |
90 |
61 |
87 |
59 |
67 |
65 |
32 |
17 |
21 |
24 |
4427 |
Sanger |
36.7 |
364 |
119.6 |
105 |
72 |
101 |
70 |
100 |
70 |
96 |
68 |
74 |
72 |
37 |
24 |
30 |
34 |
- |
Santa Ana FS |
33.8 |
115 |
117.8 |
98 |
70 |
91 |
68 |
89 |
68 |
84 |
67 |
72 |
70 |
26 |
33 |
35 |
38 |
1430 |
Santa Barbara AP |
34.4 |
9 |
119.8 |
90 |
69 |
83 |
67 |
81 |
67 |
77 |
65 |
70 |
68 |
20 |
29 |
34 |
36 |
2487 |
Santa Barbara CO |
34.4 |
5 |
119.7 |
91 |
69 |
84 |
67 |
82 |
67 |
78 |
65 |
70 |
68 |
22 |
33 |
38 |
40 |
1994 |
Santa Clara Univ |
37.4 |
88 |
121.9 |
90 |
67 |
87 |
65 |
86 |
65 |
82 |
63 |
69 |
67 |
30 |
29 |
34 |
36 |
2566 |
Santa Clarita |
34.4 |
1300 |
118.5 |
103 |
71 |
98 |
70 |
97 |
70 |
93 |
68 |
74 |
72 |
36 |
30 |
35 |
37 |
- |
Santa Cruz |
37 |
125 |
122 |
94 |
68 |
88 |
66 |
86 |
66 |
81 |
64 |
69 |
67 |
28 |
27 |
32 |
35 |
3136 |
Santa Fe Springs |
33.9 |
280 |
118.1 |
99 |
69 |
90 |
68 |
88 |
68 |
84 |
67 |
72 |
70 |
24 |
31 |
36 |
38 |
- |
Santa Maria AP |
34.9 |
236 |
120.5 |
90 |
66 |
83 |
64 |
82 |
63 |
78 |
61 |
67 |
65 |
23 |
25 |
31 |
33 |
3053 |
Santa Monica |
34 |
15 |
118.5 |
85 |
67 |
78 |
66 |
76 |
66 |
72 |
64 |
69 |
67 |
15 |
39 |
44 |
46 |
1873 |
Santa Paula |
34.4 |
263 |
119.1 |
101 |
71 |
94 |
70 |
92 |
70 |
87 |
68 |
73 |
71 |
28 |
28 |
33 |
35 |
2030 |
Santa Rosa |
38.5 |
167 |
122.8 |
99 |
69 |
96 |
68 |
95 |
68 |
92 |
66 |
71 |
69 |
35 |
24 |
27 |
29 |
2980 |
Santee |
32.8 |
400 |
117 |
96 |
69 |
91 |
68 |
90 |
68 |
87 |
67 |
72 |
70 |
20 |
25 |
30 |
33 |
- |
Saratoga |
37.3 |
500 |
122 |
96 |
67 |
88 |
66 |
86 |
66 |
80 |
65 |
70 |
68 |
31 |
27 |
32 |
35 |
- |
Sausalito |
37.9 |
10 |
122.5 |
85 |
66 |
80 |
65 |
78 |
65 |
73 |
63 |
67 |
65 |
12 |
30 |
34 |
36 |
- |
Sawyer's Bar RS |
41.3 |
2169 |
123.1 |
100 |
66 |
95 |
65 |
93 |
64 |
88 |
62 |
68 |
66 |
38 |
14 |
21 |
25 |
4102 |
Scotia |
40.5 |
139 |
124.4 |
78 |
61 |
74 |
60 |
73 |
60 |
69 |
58 |
63 |
61 |
19 |
28 |
33 |
35 |
3954 |
Scotts Valley |
37 |
400 |
122 |
94 |
68 |
88 |
66 |
86 |
66 |
81 |
64 |
69 |
67 |
28 |
27 |
32 |
35 |
1097 |
Seal Beach |
33.8 |
21 |
118.1 |
94 |
69 |
86 |
68 |
84 |
67 |
80 |
65 |
71 |
69 |
15 |
35 |
40 |
42 |
1519 |
Seaside |
36.6 |
17 |
122.9 |
85 |
66 |
79 |
64 |
77 |
64 |
73 |
62 |
67 |
65 |
20 |
30 |
35 |
37 |
- |
Sebastapol |
38.4 |
102 |
122.8 |
99 |
69 |
96 |
68 |
95 |
68 |
92 |
66 |
71 |
69 |
35 |
24 |
27 |
29 |
1249 |
Selma |
36.6 |
305 |
119.6 |
104 |
73 |
101 |
71 |
100 |
70 |
97 |
68 |
75 |
73 |
38 |
24 |
30 |
34 |
- |
Sepulveda |
34.2 |
818 |
118.5 |
103 |
71 |
98 |
69 |
96 |
69 |
92 |
67 |
74 |
71 |
32 |
28 |
33 |
36 |
664 |
Shafter |
35.5 |
345 |
119.2 |
106 |
71 |
102 |
70 |
101 |
70 |
98 |
68 |
74 |
72 |
28 |
24 |
29 |
32 |
2185 |
Shasta Dam |
40.7 |
1076 |
122.4 |
105 |
69 |
101 |
68 |
99 |
68 |
95 |
67 |
72 |
70 |
27 |
29 |
34 |
36 |
2943 |
Shelter Cove |
40 |
110 |
124.1 |
80 |
61 |
73 |
60 |
72 |
59 |
68 |
57 |
63 |
61 |
15 |
34 |
39 |
41 |
- |
Sherman Oaks |
34.2 |
657 |
118.5 |
103 |
71 |
98 |
69 |
96 |
69 |
92 |
67 |
74 |
71 |
28 |
29 |
34 |
37 |
664 |
Sierra City |
39.6 |
4230 |
120.1 |
96 |
62 |
93 |
61 |
92 |
61 |
89 |
59 |
66 |
64 |
43 |
12 |
19 |
24 |
- |
Sierra Madre |
34.2 |
1153 |
118.1 |
102 |
69 |
96 |
68 |
94 |
68 |
90 |
67 |
73 |
71 |
27 |
32 |
37 |
39 |
- |
Sierraville RS |
39.6 |
4975 |
120.4 |
94 |
60 |
91 |
59 |
90 |
59 |
86 |
57 |
64 |
62 |
44 |
-10 |
-4 |
0 |
6893 |
Signal Hill |
33.5 |
100 |
118.2 |
99 |
70 |
90 |
69 |
88 |
68 |
84 |
66 |
72 |
70 |
19 |
35 |
39 |
42 |
- |
Simi Valley |
34.4 |
500 |
118.8 |
98 |
70 |
93 |
68 |
91 |
68 |
87 |
66 |
73 |
71 |
30 |
28 |
33 |
35 |
- |
Solana Beach |
33 |
15 |
117.3 |
87 |
68 |
83 |
67 |
81 |
67 |
77 |
65 |
70 |
68 |
10 |
35 |
39 |
41 |
- |
Soledad |
36.4 |
200 |
121.3 |
90 |
67 |
87 |
65 |
86 |
65 |
82 |
64 |
70 |
67 |
23 |
24 |
29 |
32 |
1020 |
Sonoma |
38.3 |
70 |
122.5 |
101 |
70 |
96 |
69 |
94 |
69 |
90 |
67 |
72 |
70 |
40 |
22 |
28 |
31 |
2998 |
Sonora RS |
38 |
1749 |
120.4 |
103 |
68 |
100 |
67 |
99 |
67 |
95 |
66 |
72 |
70 |
34 |
20 |
26 |
29 |
3537 |
Soquel |
37 |
50 |
122 |
94 |
67 |
88 |
66 |
86 |
65 |
81 |
63 |
69 |
67 |
24 |
27 |
32 |
35 |
1097 |
South El Monte |
34 |
270 |
118.1 |
101 |
72 |
97 |
70 |
95 |
70 |
91 |
68 |
74 |
72 |
28 |
31 |
36 |
38 |
- |
South Entr Yosemite |
37.5 |
5120 |
119.6 |
92 |
61 |
88 |
60 |
87 |
60 |
84 |
59 |
64 |
62 |
36 |
8 |
15 |
20 |
5789 |
South Gate |
33.9 |
120 |
118.2 |
97 |
70 |
90 |
69 |
88 |
69 |
84 |
67 |
72 |
70 |
21 |
32 |
37 |
39 |
- |
South Laguna |
33.6 |
100 |
117.7 |
91 |
69 |
83 |
68 |
82 |
68 |
78 |
66 |
71 |
69 |
18 |
30 |
33 |
36 |
586 |
South Lake Tahoe |
38.9 |
6200 |
120 |
85 |
56 |
82 |
55 |
79 |
55 |
71 |
54 |
60 |
58 |
33 |
-2 |
3 |
10 |
- |
South Oroville |
39.5 |
174 |
121.6 |
106 |
71 |
104 |
70 |
102 |
70 |
98 |
69 |
74 |
72 |
37 |
25 |
30 |
33 |
1385 |
South Pasadena |
34 |
657 |
118.2 |
99 |
69 |
94 |
68 |
92 |
68 |
88 |
67 |
73 |
71 |
30 |
31 |
36 |
38 |
- |
South San Francisco |
37.7 |
10 |
122.4 |
87 |
67 |
81 |
64 |
78 |
64 |
72 |
62 |
68 |
65 |
20 |
32 |
36 |
38 |
- |
South San Gabriel |
34.1 |
450 |
118.1 |
99 |
70 |
94 |
69 |
92 |
69 |
88 |
68 |
73 |
71 |
73 |
30 |
35 |
37 |
431 |
South Whittier |
33.9 |
300 |
118 |
100 |
70 |
92 |
69 |
90 |
69 |
84 |
68 |
73 |
71 |
30 |
31 |
36 |
38 |
- |
South Yuba City |
39.1 |
59 |
121.6 |
105 |
69 |
101 |
69 |
100 |
69 |
96 |
68 |
72 |
71 |
36 |
24 |
29 |
32 |
1160 |
Spring Valley |
32.7 |
300 |
117 |
94 |
69 |
86 |
68 |
85 |
68 |
82 |
66 |
71 |
69 |
30 |
34 |
38 |
41 |
- |
Squaw Valley |
39.2 |
6235 |
120.2 |
88 |
57 |
85 |
56 |
84 |
56 |
80 |
54 |
61 |
59 |
40 |
-10 |
-4 |
0 |
- |
Squirrel Inn |
34.2 |
5680 |
117.2 |
86 |
61 |
82 |
60 |
81 |
60 |
77 |
58 |
65 |
63 |
23 |
12 |
18 |
22 |
5175 |
Stanford |
37.5 |
23 |
122.1 |
93 |
66 |
85 |
64 |
83 |
64 |
77 |
62 |
68 |
66 |
25 |
26 |
31 |
34 |
1103 |
Stanton |
33.6 |
45 |
118 |
98 |
69 |
91 |
68 |
89 |
68 |
84 |
67 |
72 |
70 |
24 |
31 |
36 |
38 |
- |
Stockton AP |
37.9 |
22 |
121.3 |
103 |
71 |
98 |
69 |
97 |
69 |
93 |
67 |
73 |
71 |
35 |
24 |
28 |
30 |
2806 |
Stockton FS 4 |
38 |
12 |
121.3 |
101 |
70 |
96 |
68 |
95 |
68 |
91 |
67 |
72 |
70 |
37 |
24 |
28 |
30 |
2846 |
Stony Gorge Res |
39.6 |
791 |
122.5 |
104 |
70 |
99 |
69 |
97 |
69 |
93 |
67 |
72 |
70 |
37 |
21 |
27 |
30 |
3149 |
Strawberry Valley |
39.6 |
3808 |
121.1 |
96 |
63 |
93 |
62 |
92 |
62 |
88 |
60 |
66 |
64 |
32 |
14 |
21 |
25 |
5120 |
Studio City |
34.3 |
620 |
118.4 |
102 |
70 |
97 |
69 |
95 |
69 |
91 |
67 |
73 |
71 |
31 |
28 |
33 |
36 |
664 |
Suisun City |
38.2 |
72 |
122 |
103 |
71 |
98 |
69 |
96 |
68 |
91 |
66 |
73 |
70 |
35 |
24 |
29 |
32 |
1299 |
Sun City |
33.7 |
1420 |
117.2 |
105 |
70 |
101 |
69 |
100 |
69 |
97 |
68 |
74 |
72 |
39 |
22 |
27 |
30 |
827 |
Sunland |
34.3 |
1460 |
118.3 |
107 |
71 |
102 |
70 |
100 |
70 |
96 |
68 |
74 |
72 |
36 |
28 |
33 |
36 |
- |
Sunnyvale |
37.3 |
97 |
122 |
96 |
68 |
88 |
66 |
86 |
66 |
80 |
64 |
70 |
68 |
26 |
29 |
34 |
36 |
2511 |
Susanville AP |
40.4 |
4148 |
120.6 |
98 |
62 |
95 |
61 |
94 |
61 |
90 |
59 |
66 |
64 |
38 |
-1 |
4 |
11 |
6233 |
Taft |
35.1 |
987 |
119.5 |
106 |
71 |
102 |
70 |
101 |
70 |
98 |
68 |
74 |
72 |
34 |
26 |
31 |
35 |
934 |
Tahoe City |
39.2 |
6230 |
120.1 |
84 |
56 |
81 |
55 |
80 |
55 |
76 |
53 |
60 |
58 |
36 |
2 |
7 |
14 |
8085 |
Tahoe Valley AP |
38.9 |
6254 |
120.0 |
85 |
56 |
82 |
55 |
81 |
55 |
77 |
53 |
60 |
58 |
38 |
-5 |
2 |
6 |
- |
Tamalpais-Homestead Valley |
37.9 |
25 |
122.5 |
97 |
68 |
91 |
66 |
89 |
66 |
84 |
64 |
70 |
68 |
28 |
28 |
33 |
35 |
874 |
Tarzana |
34.2 |
800 |
118.6 |
104 |
71 |
99 |
69 |
97 |
69 |
93 |
68 |
74 |
71 |
27 |
27 |
32 |
35 |
664 |
Tehachapi |
35.1 |
3975 |
118.5 |
97 |
66 |
93 |
65 |
92 |
65 |
89 |
64 |
69 |
67 |
33 |
13 |
20 |
24 |
4494 |
Tejon Rancho |
35 |
1425 |
118.8 |
107 |
71 |
103 |
70 |
102 |
70 |
99 |
68 |
74 |
72 |
27 |
24 |
29 |
32 |
2602 |
Temecula |
33.5 |
1006 |
117.2 |
101 |
69 |
96 |
68 |
95 |
68 |
91 |
67 |
73 |
71 |
34 |
24 |
29 |
32 |
- |
Temple City |
34.1 |
403 |
118.1 |
101 |
70 |
95 |
69 |
93 |
69 |
89 |
68 |
73 |
71 |
27 |
30 |
35 |
37 |
- |
Termo |
40.9 |
5300 |
120.5 |
95 |
60 |
92 |
59 |
91 |
59 |
87 |
57 |
64 |
62 |
37 |
-17 |
-11 |
-4 |
- |
Thermal AP |
33.6 |
-112 |
116.1 |
114 |
74 |
110 |
74 |
109 |
74 |
106 |
74 |
80 |
79 |
29 |
26 |
31 |
35 |
1154 |
Thermalito |
37.9 |
25 |
121.6 |
106 |
71 |
104 |
70 |
102 |
70 |
98 |
69 |
74 |
72 |
37 |
25 |
30 |
33 |
- |
Thousand Oaks |
34.2 |
810 |
118.8 |
98 |
69 |
93 |
68 |
92 |
68 |
88 |
67 |
72 |
70 |
30 |
27 |
32 |
35 |
- |
Three Rivers PH 1 |
36.5 |
1140 |
118.9 |
105 |
70 |
102 |
69 |
101 |
69 |
98 |
67 |
73 |
71 |
38 |
24 |
30 |
32 |
2642 |
Tiburon |
37.9 |
90 |
122.5 |
85 |
66 |
80 |
65 |
78 |
65 |
73 |
63 |
67 |
65 |
12 |
30 |
34 |
36 |
- |
Tiger Creek PH |
38.5 |
2355 |
120.5 |
100 |
66 |
96 |
65 |
95 |
65 |
92 |
63 |
69 |
67 |
36 |
20 |
26 |
29 |
3795 |
Torrance |
33.8 |
110 |
118.3 |
93 |
69 |
86 |
68 |
84 |
68 |
80 |
66 |
71 |
69 |
18 |
32 |
37 |
39 |
1859 |
Tracy Carbona |
37.7 |
140 |
121.4 |
102 |
70 |
97 |
68 |
95 |
68 |
90 |
67 |
72 |
70 |
38 |
24 |
29 |
32 |
2704 |
Tracy Pumps |
37.8 |
61 |
121.4 |
104 |
71 |
99 |
69 |
97 |
69 |
92 |
68 |
73 |
71 |
39 |
23 |
28 |
31 |
- |
Travis AFB |
38.3 |
72 |
121.9 |
103 |
71 |
98 |
69 |
96 |
68 |
91 |
66 |
73 |
70 |
35 |
24 |
29 |
32 |
2725 |
Trinity Dam |
40.8 |
2500 |
122.8 |
99 |
65 |
94 |
64 |
92 |
64 |
88 |
62 |
68 |
66 |
37 |
17 |
24 |
28 |
- |
Trona |
35.8 |
1695 |
117.4 |
113 |
72 |
109 |
70 |
108 |
70 |
105 |
68 |
76 |
73 |
35 |
18 |
24 |
27 |
2415 |
Truckee RS |
39.3 |
5995 |
120.2 |
90 |
58 |
87 |
57 |
86 |
57 |
82 |
55 |
62 |
60 |
40 |
-10 |
-4 |
0 |
8230 |
Tujunga |
34.3 |
1820 |
118.3 |
103 |
70 |
99 |
69 |
98 |
69 |
94 |
67 |
73 |
71 |
36 |
20 |
26 |
29 |
- |
Tulare |
36.2 |
290 |
119.4 |
105 |
72 |
101 |
71 |
100 |
71 |
96 |
69 |
74 |
72 |
39 |
24 |
30 |
34 |
- |
Tulelake |
42 |
4035 |
121.5 |
92 |
60 |
88 |
59 |
87 |
59 |
83 |
57 |
63 |
61 |
41 |
-5 |
0 |
6 |
6854 |
Turlock |
37.5 |
100 |
120.9 |
104 |
72 |
100 |
70 |
99 |
70 |
95 |
68 |
74 |
72 |
40 |
24 |
30 |
34 |
- |
Turntable Creek |
40.8 |
1067 |
120.9 |
105 |
69 |
101 |
68 |
99 |
68 |
95 |
66 |
72 |
70 |
28 |
24 |
29 |
32 |
- |
Tustin Foothills |
33.8 |
500 |
117.8 |
99 |
71 |
92 |
69 |
90 |
69 |
85 |
68 |
73 |
71 |
27 |
28 |
31 |
34 |
550 |
Tustin Irvine Rch |
33.7 |
118 |
117.8 |
99 |
71 |
92 |
69 |
90 |
69 |
85 |
68 |
73 |
71 |
27 |
28 |
31 |
34 |
1856 |
Twentynine Palms |
34.1 |
1975 |
116.1 |
110 |
71 |
107 |
70 |
106 |
70 |
103 |
69 |
76 |
74 |
31 |
21 |
26 |
29 |
1973 |
Twin Lakes |
38.7 |
7829 |
119.1 |
73 |
49 |
64 |
47 |
62 |
47 |
57 |
46 |
53 |
50 |
30 |
-7 |
-2 |
4 |
9196 |
Twitchell Dam |
35 |
582 |
120.3 |
99 |
70 |
93 |
68 |
92 |
68 |
88 |
66 |
71 |
69 |
26 |
26 |
31 |
34 |
- |
UCLA |
34.1 |
430 |
118.4 |
93 |
69 |
86 |
68 |
84 |
68 |
80 |
66 |
71 |
69 |
20 |
39 |
43 |
46 |
1509 |
Ukiah |
39.2 |
623 |
123.2 |
100 |
70 |
97 |
69 |
96 |
69 |
92 |
68 |
72 |
71 |
42 |
22 |
28 |
31 |
2958 |
Union City |
37.6 |
5 |
122.1 |
90 |
67 |
87 |
66 |
85 |
65 |
81 |
63 |
69 |
67 |
20 |
25 |
30 |
33 |
- |
Upland |
34.1 |
1605 |
117.7 |
102 |
69 |
98 |
68 |
96 |
68 |
92 |
66 |
73 |
71 |
31 |
29 |
34 |
36 |
2175 |
Upper Lake RS |
39.2 |
1347 |
123 |
98 |
68 |
95 |
67 |
94 |
66 |
91 |
64 |
73 |
71 |
39 |
18 |
34 |
36 |
- |
Upper San Leandro |
37.8 |
394 |
122.1 |
93 |
67 |
87 |
66 |
85 |
65 |
80 |
63 |
69 |
67 |
22 |
28 |
33 |
35 |
- |
Vacaville |
38.4 |
105 |
122 |
103 |
71 |
100 |
70 |
98 |
70 |
94 |
68 |
73 |
71 |
40 |
23 |
28 |
31 |
2788 |
Valinda |
34 |
340 |
117.9 |
102 |
70 |
98 |
69 |
96 |
69 |
92 |
68 |
74 |
72 |
28 |
31 |
36 |
38 |
- |
Valle Vista |
33.8 |
1655 |
116.9 |
109 |
70 |
104 |
69 |
103 |
69 |
101 |
67 |
74 |
72 |
40 |
20 |
25 |
28 |
- |
Vallejo |
38.1 |
85 |
122.3 |
93 |
67 |
90 |
66 |
88 |
66 |
84 |
64 |
70 |
68 |
23 |
28 |
33 |
36 |
- |
Valyermo RS |
34.5 |
3600 |
117.9 |
100 |
67 |
96 |
66 |
95 |
66 |
91 |
65 |
70 |
68 |
41 |
12 |
19 |
24 |
3870 |
Van Nuys |
34.2 |
708 |
118.5 |
103 |
71 |
98 |
69 |
96 |
69 |
92 |
67 |
74 |
71 |
30 |
28 |
33 |
39 |
664 |
Vandenburg AFB |
34.7 |
368 |
122.8 |
85 |
62 |
77 |
61 |
75 |
61 |
71 |
60 |
64 |
62 |
16 |
30 |
35 |
37 |
3451 |
Ventura |
34.3 |
341 |
119.3 |
89 |
68 |
82 |
67 |
80 |
67 |
76 |
66 |
70 |
68 |
15 |
29 |
34 |
36 |
- |
Victorville Pumps |
34.5 |
2858 |
117.3 |
105 |
67 |
101 |
65 |
100 |
64 |
97 |
62 |
70 |
68 |
39 |
14 |
24 |
27 |
3191 |
View Park |
34 |
300 |
118.3 |
95 |
69 |
88 |
68 |
85 |
68 |
78 |
66 |
71 |
69 |
18 |
36 |
40 |
43 |
- |
Villa Park |
33.8 |
300 |
117.8 |
99 |
70 |
92 |
68 |
90 |
68 |
85 |
67 |
72 |
70 |
27 |
33 |
37 |
40 |
550 |
Vincent |
34.5 |
3135 |
118.1 |
105 |
67 |
101 |
65 |
100 |
65 |
96 |
64 |
71 |
69 |
33 |
10 |
18 |
22 |
1455 |
Visalia |
36.3 |
325 |
119.3 |
103 |
71 |
100 |
70 |
99 |
70 |
96 |
69 |
73 |
72 |
38 |
25 |
30 |
33 |
2459 |
Vista |
33.2 |
510 |
117.2 |
96 |
69 |
90 |
68 |
89 |
68 |
85 |
67 |
72 |
70 |
16 |
30 |
35 |
37 |
- |
Volta PH |
40.5 |
2220 |
120.9 |
101 |
66 |
98 |
65 |
97 |
65 |
93 |
63 |
69 |
67 |
33 |
21 |
27 |
30 |
- |
Walnut |
34 |
550 |
117.9 |
101 |
70 |
97 |
69 |
96 |
69 |
92 |
69 |
74 |
72 |
30 |
28 |
33 |
35 |
- |
Walnut Creek |
37.9 |
245 |
122.1 |
100 |
69 |
94 |
67 |
92 |
67 |
87 |
66 |
71 |
69 |
32 |
23 |
29 |
31 |
- |
Walnut Grove |
38.2 |
23 |
121.5 |
102 |
70 |
98 |
69 |
96 |
69 |
92 |
68 |
72 |
71 |
37 |
24 |
30 |
32 |
- |
Walnut Park |
33.9 |
45 |
118.2 |
92 |
69 |
84 |
68 |
82 |
68 |
78 |
66 |
71 |
69 |
12 |
37 |
42 |
44 |
450 |
Warner Springs |
33.3 |
3180 |
116.6 |
100 |
67 |
95 |
66 |
94 |
66 |
91 |
65 |
71 |
69 |
40 |
15 |
22 |
26 |
3591 |
Wasco |
35.6 |
333 |
119.3 |
105 |
71 |
101 |
70 |
100 |
70 |
97 |
68 |
74 |
72 |
36 |
23 |
28 |
31 |
2466 |
Watsonville |
36.9 |
95 |
121.8 |
86 |
66 |
82 |
64 |
81 |
63 |
79 |
61 |
68 |
65 |
22 |
28 |
33 |
35 |
3418 |
Weaverville RS |
40.7 |
2050 |
122.9 |
100 |
67 |
95 |
66 |
93 |
65 |
89 |
63 |
69 |
67 |
46 |
10 |
17 |
22 |
4992 |
Weed FD |
41.4 |
3590 |
122.4 |
92 |
63 |
89 |
62 |
88 |
61 |
84 |
59 |
65 |
63 |
35 |
4 |
12 |
17 |
- |
West Athens |
33.9 |
25 |
118.3 |
92 |
69 |
85 |
68 |
84 |
68 |
80 |
66 |
71 |
69 |
18 |
32 |
37 |
39 |
450 |
West Carson |
33.8 |
100 |
118.3 |
92 |
69 |
87 |
68 |
85 |
68 |
81 |
66 |
71 |
69 |
18 |
32 |
37 |
39 |
- |
West Compton |
33.9 |
71 |
118.3 |
97 |
69 |
90 |
68 |
88 |
68 |
83 |
67 |
72 |
70 |
21 |
33 |
37 |
39 |
450 |
West Covina |
34 |
365 |
117.9 |
102 |
70 |
98 |
69 |
96 |
69 |
92 |
68 |
74 |
72 |
34 |
29 |
34 |
36 |
- |
West Hollywood |
34 |
290 |
118.4 |
95 |
70 |
89 |
69 |
87 |
69 |
82 |
67 |
72 |
70 |
20 |
38 |
42 |
45 |
- |
West Pittsburg |
38 |
12 |
121.9 |
102 |
70 |
97 |
68 |
95 |
68 |
90 |
67 |
72 |
70 |
34 |
26 |
32 |
35 |
- |
West Puente Valley |
34 |
500 |
117.9 |
101 |
71 |
97 |
70 |
95 |
70 |
91 |
68 |
73 |
71 |
26 |
31 |
36 |
39 |
- |
West Sacramento |
38.6 |
19 |
121.5 |
104 |
72 |
100 |
70 |
98 |
70 |
94 |
68 |
74 |
71 |
35 |
26 |
31 |
33 |
1290 |
West Whittier-Los Nietos |
34 |
320 |
118.1 |
99 |
69 |
90 |
68 |
88 |
68 |
84 |
67 |
72 |
70 |
24 |
31 |
35 |
38 |
- |
Westlake Village |
34.2 |
750 |
118.8 |
103 |
71 |
99 |
70 |
98 |
70 |
94 |
69 |
73 |
71 |
26 |
26 |
30 |
33 |
- |
Westminster |
33.8 |
38 |
118 |
95 |
70 |
88 |
68 |
86 |
68 |
81 |
67 |
72 |
70 |
23 |
33 |
38 |
41 |
- |
Westmont |
33.9 |
110 |
118.3 |
96 |
70 |
89 |
69 |
87 |
69 |
83 |
67 |
72 |
70 |
20 |
36 |
41 |
44 |
400 |
Whiskeytown Res |
40.6 |
1295 |
122.6 |
105 |
69 |
101 |
68 |
100 |
68 |
96 |
67 |
72 |
70 |
31 |
25 |
30 |
33 |
- |
White Mtn 1 |
37.5 |
10150 |
119.3 |
73 |
49 |
69 |
47 |
68 |
47 |
65 |
45 |
53 |
50 |
37 |
-15 |
-9 |
-6 |
- |
White Mtn 2 |
37.6 |
12470 |
119.3 |
61 |
42 |
58 |
41 |
57 |
41 |
54 |
40 |
46 |
43 |
38 |
-20 |
-15 |
-12 |
- |
Whittier |
34 |
320 |
118 |
99 |
69 |
90 |
68 |
88 |
68 |
84 |
67 |
72 |
70 |
24 |
31 |
35 |
38 |
- |
Wildomar |
33.6 |
1255 |
117.3 |
103 |
70 |
99 |
69 |
98 |
69 |
94 |
68 |
74 |
72 |
36 |
23 |
28 |
30 |
827 |
Wildrose RS |
36.3 |
4100 |
|
100 |
64 |
97 |
63 |
96 |
63 |
93 |
61 |
68 |
66 |
33 |
13 |
20 |
24 |
- |
Williams |
39.2 |
85 |
122.2 |
104 |
71 |
100 |
70 |
98 |
70 |
94 |
68 |
73 |
71 |
36 |
24 |
29 |
32 |
- |
Willits |
39.4 |
1350 |
123.3 |
95 |
66 |
89 |
65 |
87 |
64 |
82 |
62 |
68 |
66 |
38 |
18 |
24 |
27 |
- |
Willow Brook |
33.9 |
60 |
118.2 |
97 |
70 |
90 |
69 |
88 |
69 |
83 |
67 |
72 |
70 |
21 |
35 |
39 |
42 |
- |
Willow Creek |
41 |
461 |
123 |
104 |
70 |
98 |
68 |
96 |
68 |
92 |
66 |
71 |
69 |
35 |
22 |
28 |
31 |
- |
Willows |
39.5 |
140 |
122.2 |
104 |
71 |
100 |
70 |
98 |
70 |
94 |
68 |
73 |
71 |
36 |
22 |
28 |
31 |
2836 |
Windsor |
38.5 |
130 |
122.8 |
99 |
69 |
96 |
68 |
95 |
68 |
92 |
66 |
71 |
69 |
35 |
24 |
27 |
29 |
1249 |
Winters |
38.5 |
135 |
122 |
104 |
71 |
99 |
70 |
97 |
70 |
93 |
68 |
73 |
71 |
38 |
24 |
29 |
32 |
2593 |
Winton |
37.4 |
168 |
120.6 |
103 |
71 |
100 |
69 |
99 |
69 |
95 |
67 |
73 |
71 |
36 |
21 |
27 |
30 |
1244 |
Woodcrest |
33.9 |
1500 |
117.4 |
104 |
70 |
100 |
69 |
99 |
68 |
95 |
65 |
74 |
72 |
37 |
27 |
32 |
35 |
611 |
Woodfords |
38.8 |
5671 |
119.8 |
92 |
59 |
89 |
58 |
88 |
58 |
84 |
56 |
63 |
61 |
32 |
0 |
5 |
12 |
6047 |
Woodlake |
36.3 |
500 |
119.1 |
103 |
71 |
100 |
70 |
99 |
70 |
96 |
69 |
73 |
72 |
38 |
25 |
30 |
33 |
1130 |
Woodland |
38.7 |
69 |
121.8 |
106 |
72 |
101 |
71 |
100 |
71 |
96 |
69 |
74 |
72 |
40 |
25 |
30 |
33 |
2708 |
Woodland Hills |
34.2 |
944 |
118.6 |
104 |
71 |
99 |
70 |
97 |
70 |
93 |
68 |
74 |
72 |
32 |
26 |
31 |
34 |
664 |
Woodside |
37.5 |
75 |
122.3 |
92 |
67 |
84 |
66 |
82 |
65 |
76 |
63 |
69 |
67 |
24 |
22 |
28 |
31 |
- |
Yorba Linda |
33.9 |
350 |
117.8 |
102 |
70 |
94 |
69 |
92 |
69 |
88 |
68 |
73 |
71 |
31 |
30 |
35 |
37 |
1643 |
Yosemite Park Hq |
37.7 |
3970 |
119.6 |
97 |
63 |
94 |
62 |
93 |
62 |
90 |
60 |
67 |
65 |
38 |
11 |
18 |
23 |
4785 |
Yreka |
41.7 |
2625 |
122.6 |
99 |
66 |
95 |
65 |
94 |
65 |
90 |
64 |
69 |
67 |
39 |
8 |
15 |
20 |
5395 |
Yuba City |
39.1 |
70 |
121.6 |
105 |
69 |
101 |
69 |
100 |
69 |
96 |
68 |
72 |
71 |
36 |
24 |
29 |
32 |
- |
Yucaipa |
34 |
2600 |
117 |
106 |
68 |
102 |
67 |
101 |
67 |
98 |
65 |
73 |
71 |
35 |
27 |
32 |
35 |
- |
Yucca Valley |
34.2 |
2600 |
116.4 |
108 |
71 |
105 |
70 |
104 |
70 |
101 |
69 |
75 |
73 |
32 |
19 |
24 |
27 |
862 |