The following tables contain a limited list of lamp and ballast combinations. These tables provide an alternate voluntary option to the provision in Section 130(c) for determining luminaire power for any lamp and ballast combination specifically listed in Appendix NA8. This appendix is not intended to list all possible lamp and ballast combinations, and shall not to be used to determine luminaire power for any lighting system not specifically listed in this appendix.
Table NA8-1 – Fluorescent U-Tubes
Type |
Lamps - Number |
Lamps - Designation |
Ballasts - Number |
Ballasts - Designation |
Ballasts - Description |
System Watts |
2 ft. Fluorescent U-Tube T8 |
1 |
FB31T8/F32T8U |
1 |
ELECT NO |
Electronic Normal Output |
39 |
2 ft. Fluorescent U-Tube T8 |
2 |
FB31T8/F32T8U |
1 |
ELECT NO |
Electronic Normal Output |
62 |
2 ft. Fluorescent U-Tube T8 |
3 |
FB31T8/F32T8U |
1 |
ELECT NO |
Electronic Normal Output |
92 |
2 ft. Fluorescent U-Tube T8 |
1 |
FB31T8/F32T8U |
1 |
ELECT DIM |
Electronic Dimming |
33 |
2 ft. Fluorescent U-Tube T8 |
2 |
FB31T8/F32T8U |
1 |
ELECT DIM |
Electronic Dimming |
64 |
2 ft. Fluorescent U-Tube T8 |
3 |
FB31T8/F32T8U |
1 |
ELECT DIM |
Electronic Dimming |
93 |
2 ft. Fluorescent U-Tube T8 |
4 |
FB31T8/F32T8U |
1 |
ELECT DIM |
Electronic Dimming |
116 |
NO = ballast factor 85 to 100%
Table NA8-2 – Fluorescent Linear Lamps T5
Type |
Lamps - Number |
Lamps Designation |
Ballasts - Number |
Ballasts - Designation |
Ballasts - Description |
System Watts |
~23” Fluorescent Program Start T5 (14W) |
1 |
F14T5 |
1 |
ELECT |
Elect. Program Start BF=1 |
18 |
~23” Fluorescent Program Start T5 (14W) |
2 |
F14T5 |
1 |
ELECT |
Elect. Program Start BF=1 |
34 |
~34.5” Fluorescent Program Start T5 (21W) |
1 |
F21T5 |
1 |
ELECT |
Elect. Program Start BF=1 |
27 |
~34.5” Fluorescent Program Start T5 (21W) |
2 |
F21T5 |
1 |
ELECT |
Elect. Program Start BF=1 |
50 |
~46” Fluorescent Program Start T5 (28W) |
1 |
F28T5 |
1 |
ELECT |
Elect. Program Start BF=1 |
30 |
~46” Fluorescent Program Start T5 (28W) |
2 |
F28T5 |
1 |
ELECT |
Elect. Program Start BF=1 |
60 |
~58.5” Fluorescent Program Start T5 (35W) |
1 |
F35T5 |
1 |
ELECT |
Elect. Program Start BF=1 |
40 |
~58.5” Fluorescent Program Start T5 (35W) |
2 |
F35T5 |
1 |
ELECT |
Elect. Program Start BF=1 |
78 |
~23” Fluorescent Program Start T5 High Output (24W) |
1 |
F24T5HO |
1 |
ELECT |
Elect. Program Start BF=1 |
29 |
~23” Fluorescent Program Start T5 High Output (24W) |
2 |
F24T5HO |
1 |
ELECT |
Elect. Program Start BF=1 |
55 |
~34.5” Fluorescent Program Start T5 High Output(39W) |
1 |
F39T5 |
1 |
ELECT |
Elect. Program Start BF=1 |
43 |
~34.5” Fluorescent Program Start T5 High Output(39W) |
2 |
F39T5 |
1 |
ELECT |
Elect. Program Start BF=1 |
85 |
~46” Fluorescent Program Start T5 High Output (54W) |
1 |
F54T5 |
1 |
ELECT |
Elect. Program Start BF=1 |
62 |
~46” Fluorescent Program Start T5 High Output (54W) |
2 |
F54T5 |
1 |
ELECT |
Elect. Program Start BF=1 |
121 |
~46” Fluorescent Program Start T5 High Output (54W) |
1 |
F54T5 |
1 |
ELECT DIM |
Elect. Dimming |
63 |
~46” Fluorescent Program Start T5 High Output (54W) |
2 |
F54T5 |
1 |
ELECT DIM |
Elect. Dimming |
125 |
~57.5” Fluorescent Program Start T5 High Output (80W) |
1 |
ºF80T5 |
1 |
ELECT |
Elect. Program Start BF=1 |
90 |
Table NA8-3 – Fluorescent Rapid Start T-8
Type |
Lamps Num-ber |
Lamps Desig-nation |
Ballasts Num-ber |
Ballasts Desig-nation |
Ballasts Descrip-tion |
System Watts | ||
2 foot Fluorescent Rapid Start T8 (17W) Electronic Ballasts |
1 |
F17T8 |
1 |
ELECT NO |
Electronic Normal Output |
22 | ||
2 foot Fluorescent Rapid Start T8 (17W) Electronic Ballasts |
2 |
F17T8 |
1 |
ELECT NO |
Electronic Normal Output |
33 | ||
2 foot Fluorescent Rapid Start T8 (17W) Electronic Ballasts |
3 |
F17T8 |
1 |
ELECT NO |
Electronic Normal Output |
53 | ||
2 foot Fluorescent Rapid Start T8 (17W) Electronic Ballasts |
3 |
F17T8 |
2 |
ELECT NO |
Electronic Normal Output |
55 | ||
2 foot Fluorescent Rapid Start T8 (17W) Electronic Ballasts |
4 |
F17T8 |
1 |
ELECT NO |
Electronic Normal Output |
63 | ||
2 foot Fluorescent Rapid Start T8 (17W) |
1 |
F17T8 |
1 |
ELECT DIM |
Electronic Dimming |
20 | ||
2 foot Fluorescent Rapid Start T8 (17W) |
2 |
F17T8 |
1 |
ELECT DIM |
Electronic Dimming |
37 | ||
2 foot Fluorescent Rapid Start T8 (17W) |
3 |
F17T8 |
1 |
ELECT DIM |
Electronic Dimming |
56 | ||
2 foot Fluorescent Rapid Start T8 (17W) |
4 |
F17T8 |
1 |
ELECT DIM |
Electronic Dimming |
69 | ||
3 foot Fluorescent Rapid Start T8 (25W) Electronic Ballasts |
1 |
F25T8 |
1 |
ELECT NO |
Electronic Normal Output |
27 | ||
3 foot Fluorescent Rapid Start T8 (25W) Electronic Ballasts |
2 |
F25T8 |
1 |
ELECT NO |
Electronic Normal Output |
48 | ||
3 foot Fluorescent Rapid Start T8 (25W) Electronic Ballasts |
3 |
F25T8 |
1 |
ELECT NO |
Electronic Normal Output |
68 | ||
3 foot Fluorescent Rapid Start T8 (25W) Electronic Ballasts |
4 |
F25T8 |
1 |
ELECT NO |
Electronic Normal Output |
89 | ||
3 foot Fluorescent Rapid Start T8 (25W) Electronic Ballasts |
1 |
F25T8 |
1 |
ELECT RO |
Electronic Reduced Output |
24 | ||
3 foot Fluorescent Rapid Start T8 (25W) Electronic Ballasts |
2 |
F25T8 |
1 |
ELECT RO |
Electronic Reduced Output |
41 | ||
3 foot Fluorescent Rapid Start T8 (25W) Electronic Ballasts |
3 |
F25T8 |
1 |
ELECT RO |
Electronic Reduced Output |
59 | ||
3 foot Fluorescent Rapid Start T8 (25W) Electronic Ballasts |
4 |
F25T8 |
1 |
ELECT RO |
Electronic Reduced Output |
76 | ||
3 foot Fluorescent Rapid Start T8 (25W) Electronic Ballasts |
1 |
F25T8 |
1 |
ELECT HO |
Electronic High Output |
29 | ||
3 foot Fluorescent Rapid Start T8 (25W) Electronic Ballasts |
2 |
F25T8 |
1 |
ELECT HO |
Electronic High Output |
51 | ||
3 foot Fluorescent Rapid Start T8 (25W) Electronic Ballasts |
3 |
F25T8 |
1 |
ELECT HO |
Electronic High Output |
74 | ||
3 foot Fluorescent Rapid Start T8 (25W) Electronic Ballasts |
1 |
F25T8 |
1 |
ELECT DIM |
Electronic Dimming |
25 | ||
3 foot Fluorescent Rapid Start T8 (25W) Electronic Ballasts |
2 |
F25T8 |
1 |
ELECT DIM |
Electronic Dimming |
49 | ||
3 foot Fluorescent Rapid Start T8 (25W) Electronic Ballasts |
3 |
F25T8 |
1 |
ELECT DIM |
Electronic Dimming |
76 | ||
3 foot Fluorescent Rapid Start T8 (25W) Electronic Ballasts |
4 |
F25T8 |
1 |
ELECT DIM |
Electronic Dimming |
96 |
4 foot Fluorescent Instant Start T8 (“Energy Saving” 30W) |
1 |
F32T8/30ES |
1 |
ELECT NO |
Electronic Normal Output |
29 |
4 foot Fluorescent Instant Start T8 (“Energy Saving” 30W) |
2 |
F32T8/30ES |
1 |
ELECT NO |
Electronic Normal Output |
54 |
4 foot Fluorescent Instant Start T8 (“Energy Saving” 30W) |
3 |
F32T8/30ES |
1 |
ELECT NO |
Electronic Normal Output |
79 |
4 foot Fluorescent Instant Start T8 (“Energy Saving” 30W) |
4 |
F32T8/30ES |
1 |
ELECT NO |
Electronic Normal Output |
104 |
4 foot Fluorescent Instant Start T8 (“Energy Saving” 30W) |
1 |
F32T8/30ES |
1 |
ELECT RO |
Electronic Reduced Output |
27 |
4 foot Fluorescent Instant Start T8 (“Energy Saving” 30W) |
2 |
F32T8/30ES |
1 |
ELECT RO |
Electronic Reduced Output |
48 |
4 foot Fluorescent Instant Start T8 (“Energy Saving” 30W) |
3 |
F32T8/30ES |
1 |
ELECT RO |
Electronic Reduced Output |
70 |
4 foot Fluorescent Instant Start T8 (“Energy Saving” 30W) |
4 |
F32T8/30ES |
1 |
ELECT RO |
Electronic Reduced Output |
91 |
4 foot Fluorescent Instant Start T8 (“Energy Saving” 30W) |
1 |
F32T8/30ES |
1 |
ELECT NO EE |
EE Normal Output |
33 |
4 foot Fluorescent Instant Start T8 (“Energy Saving” 30W) |
2 |
F32T8/30ES |
1 |
ELECT NO EE |
Energy efficiency Normal Output |
52 |
4 foot Fluorescent Instant Start T8 (“Energy Saving” 30W) |
3 |
F32T8/30ES |
1 |
ELECT NO EE |
Energy efficiency Normal Output |
77 |
4 foot Fluorescent Instant Start T8 (“Energy Saving” 30W) |
4 |
F32T8/30ES |
1 |
ELECT NO EE |
Energy efficiency Normal Output |
101 |
4 foot Fluorescent Instant Start T8 (“Energy Saving” 30W) |
1 |
F32T8/30ES |
1 |
ELECT RO EE |
EE Reduced Output |
28 |
4 foot Fluorescent Instant Start T8 (“Energy Saving” 30W) |
2 |
F32T8/30ES |
1 |
ELECT RO EE |
EE Reduced Output |
45 |
4 foot Fluorescent Instant Start T8 (“Energy Saving” 30W) |
3 |
F32T8/30ES |
1 |
ELECT RO EE |
EE Reduced Output |
66 |
4 foot Fluorescent Instant Start T8 (“Energy Saving” 30W) |
4 |
F32T8/30ES |
1 |
ELECT RO EE |
EE Reduced Output |
88 |
4 foot Fluorescent Rapid Start T8 (32W) |
1 |
F32T8 |
1 |
ELECT NO |
Electronic Normal Output |
32 |
4 foot Fluorescent Rapid Start T8 (32W) |
2 |
F32T8 |
1 |
ELECT NO |
Electronic Normal Output |
62 |
4 foot Fluorescent Rapid Start T8 (32W) |
3 |
F32T8 |
1 |
ELECT NO |
Electronic Normal Output |
93 |
4 foot Fluorescent Rapid Start T8 (32W) |
4 |
F32T8 |
1 |
ELECT NO |
Electronic Normal Output |
114 |
4 foot Fluorescent Rapid Start T8 (32W) |
1 |
F32T8 |
1 |
EE NO |
EE Normal Output |
35 |
4 foot Fluorescent Rapid Start T8 (32W) |
2 |
F32T8 |
1 |
EE NO |
EE Normal Output |
55 |
4 foot Fluorescent Rapid Start T8 (32W) |
3 |
F32T8 |
1 |
EE NO |
EE Normal Output |
82 |
4 foot Fluorescent Rapid Start T8 (32W) |
4 |
F32T8 |
1 |
EE NO |
EE Normal Output |
107 |
4 foot Fluorescent Rapid Start T8 (32W) |
1 |
F32T8 |
1 |
ELECT RO |
Electronic Reduced Output |
29 |
4 foot Fluorescent Rapid Start T8 (32W) |
2 |
F32T8 |
1 |
ELECT RO |
Electronic Reduced Output |
51 |
4 foot Fluorescent Rapid Start T8 (32W) |
3 |
F32T8 |
1 |
ELECT RO |
Electronic Reduced Output |
76 |
4 foot Fluorescent Rapid Start T8 (32W) |
4 |
F32T8 |
1 |
ELECT RO |
Electronic Reduced Output |
98 |
4 foot Fluorescent Rapid Start T8 (32W) |
2 |
F32T8 |
1 |
ELECT HO |
Electronic High Output |
77 |
4 foot Fluorescent Rapid Start T8 (32W) |
3 |
F32T8 |
1 |
ELECT HO |
Electronic High Output |
112 |
4 foot Fluorescent Rapid Start T8 (32W) |
1 |
F32T8 |
1 |
EE RO |
EE Reduced Output |
30 |
4 foot Fluorescent Rapid Start T8 (32W) |
2 |
F32T8 |
1 |
EE RO |
EE Reduced Output |
48 |
4 foot Fluorescent Rapid Start T8 (32W) |
3 |
F32T8 |
1 |
EE RO |
EE Reduced Output |
73 |
4 foot Fluorescent Rapid Start T8 (32W) |
4 |
F32T8 |
1 |
EE RO |
EE Reduced Output |
96 |
4 foot Fluorescent Rapid Start T8 (32W) |
2 |
F32T8 |
1 |
ELECT TL |
Electronic Two Level (50 & 100%) |
65 |
4 foot Fluorescent Rapid Start T8 (32W) |
1 |
F32T8 |
1 |
ELECT DIM1 |
Electronic Dimming |
35 |
4 foot Fluorescent Rapid Start T8 (32W) |
2 |
F32T8 |
1 |
ELECT DIM1 |
Electronic Dimming |
68 |
4 foot Fluorescent Rapid Start T8 (32W) |
3 |
F32T8 |
1 |
ELECT DIM1 |
Electronic Dimming |
102 |
4 foot Fluorescent Rapid Start T8 (32W) |
1 |
F32T8 |
1 |
ELECT DIM2 |
Electronic Dimming |
33 |
4 foot Fluorescent Rapid Start T8 (32W) |
2 |
F32T8 |
1 |
ELECT DIM2 |
Electronic Dimming |
64 |
4 foot Fluorescent Rapid Start T8 (32W) |
3 |
F32T8 |
1 |
ELECT DIM2 |
Electronic Dimming |
93 |
4 foot Fluorescent Rapid Start T8 (32W) |
4 |
F32T8 |
1 |
ELECT DIM2 |
Electronic Dimming |
116 |
5 foot Fluorescent Rapid Start T8 (40W) |
1 |
F40T8 |
1 |
ELECT |
Electronic |
46 |
5 foot Fluorescent Rapid Start T8 (40W) |
2 |
F40T8 |
1 |
ELECT |
Electronic |
79 |
5 foot Fluorescent Rapid Start T8 (40W) |
3 |
F40T8 |
1 |
ELECT |
Electronic |
112 |
RO = ballast factor 70 to 85% NO = ballast factor 85 to 100% HO = ballast factor >100%
Table NA8-4 – Fluorescent Rapid Start High Output (HO) T8, 8 ft
Type |
Lamps - Number |
Lamps - Designation |
Ballasts - Number |
Ballasts - Designation |
Ballasts - Description |
System Watts |
8 foot Fluorescent Rapid Start T8 High Output (86W) |
1 |
F96T8/HO |
1 |
ELECT |
Electronic |
88 |
8 foot Fluorescent Rapid Start T8 High Output (86W) |
2 |
F96T8/HO |
1 |
ELECT |
Electronic |
160 |
HO = ballast factor >100%
Table NA8-5 – High Intensity Discharge
Type |
Lamps - Number |
Lamps - Designation |
Ballasts Number |
Ballasts - Designation |
Ballasts - Description |
System Watts |
Comment |
Metal Halide |
1 |
M35/39 |
1 |
MAG STD |
Mag. Stand. |
58 |
|
Metal Halide |
1 |
M35/39 |
1 |
ELECT |
Electronic |
44 |
|
Metal Halide |
1 |
M50 |
1 |
MAG STD |
Mag. Stand. |
67 |
|
Metal Halide |
1 |
M50 |
1 |
ELECT |
Electronic |
58 |
|
Metal Halide |
1 |
M70 |
1 |
MAG STD |
Mag. Stand. |
95 |
|
Metal Halide |
1 |
M70 |
1 |
ELECT |
Electronic |
86 |
|
Metal Halide |
1 |
M100 |
1 |
MAG STD |
Mag. Stand. |
130 |
|
Metal Halide |
1 |
M100 |
1 |
ELECT |
Electronic |
110 |
|
Metal Halide |
1 |
M150 |
1 |
MAG STD |
Mag. Stand. |
185 |
|
Metal Halide |
1 |
M150 |
1 |
ELECT |
Electronic |
168 |
|
Metal Halide |
1 |
M175 |
1 |
MAG STD |
Mag. Stand. |
208 |
|
Metal Halide |
1 |
M175 |
1 |
ELECT |
Electronic |
194 |
|
Metal Halide |
1 |
M200 |
1 |
MAG STD |
Mag. Stand. |
232 |
|
Metal Halide |
1 |
M250 |
1 |
MAG STD |
Mag. Stand. |
295 |
|
Metal Halide |
1 |
M250 |
1 |
ELECT |
Electronic |
269 |
|
Metal Halide |
1 |
M320 |
1 |
MAG STD |
Mag. Stand. |
368 |
|
Metal Halide |
1 |
M320 |
1 |
ELECT |
Electronic |
343 |
|
Metal Halide |
1 |
M360 |
1 |
MAG STD |
Mag. Stand. |
422 |
|
Metal Halide |
1 |
M400 |
1 |
MAG STD |
Mag. Stand. |
452 |
|
Metal Halide |
1 |
M400 |
1 |
ELECT |
Electronic |
430 |
|
Metal Halide |
1 |
M450 |
1 |
MAG STD |
Mag. Stand. |
508 |
|
Metal Halide |
1 |
M750 |
1 |
MAG STD |
Mag. Stand. |
818 |
|
Metal Halide |
1 |
M1000 |
1 |
MAG STD |
Mag. Stand. |
1080 |
|
Metal Halide |
1 |
M1500 |
1 |
MAG STD |
Mag. Stand. |
1605 |
|
High Pressure Sodium |
1 |
S35 |
1 |
MAG STD |
Mag. Stand. |
47 |
|
High Pressure Sodium |
1 |
S50 |
1 |
MAG STD |
Mag. Stand. |
66 |
|
High Pressure Sodium |
1 |
S70 |
1 |
MAG STD |
Mag. Stand. |
91 |
|
High Pressure Sodium |
1 |
S100 |
1 |
MAG STD |
Mag. Stand. |
128 |
|
High Pressure Sodium |
1 |
S150 |
1 |
MAG STD |
Mag. Stand. |
188 |
|
High Pressure Sodium |
1 |
S200 |
1 |
MAG STD |
Mag. Stand. |
230 |
|
High Pressure Sodium |
1 |
S250 |
1 |
MAG STD |
Mag. Stand. |
295 |
|
High Pressure Sodium |
1 |
S400 |
1 |
MAG STD |
Mag. Stand. |
464 |
|
High Pressure Sodium |
1 |
S1000 |
1 |
MAG STD |
Mag. Stand. |
1100 |
|
Table NA8-6 –12
Volt Tungsten Halogen Lamps Including MR16, Bi-pin, AR70, AR111, PAR36
(Shall
NOT apply to track lighting systems)
Type |
Lamps - Number |
Lamps - Designation |
Ballasts - Number |
Ballasts - Designation |
Ballasts - Description |
System Watts |
Comment |
High Pressure Sodium |
1 |
20 watt lamp |
1 |
ELECT |
Electronic Power Supply |
23 |
|
High Pressure Sodium |
1 |
25 watt lamp |
1 |
ELECT |
Electronic Power Supply |
28 |
|
High Pressure Sodium |
1 |
35 watt lamp |
1 |
ELECT |
Electronic Power Supply |
38 |
|
High Pressure Sodium |
1 |
37 watt lamp |
1 |
ELECT |
Electronic Power Supply |
41 |
|
High Pressure Sodium |
1 |
42 watt lamp |
1 |
ELECT |
Electronic Power Supply |
45 |
|
High Pressure Sodium |
1 |
50 watt lamp |
1 |
ELECT |
Electronic Power Supply |
54 |
|
High Pressure Sodium |
1 |
65 watt lamp |
1 |
ELECT |
Electronic Power Supply |
69 |
|
High Pressure Sodium |
1 |
71 watt lamp |
1 |
ELECT |
Electronic Power Supply |
75 |
|
High Pressure Sodium |
1 |
75 watt lamp |
1 |
ELECT |
Electronic Power Supply |
80 |
|
High Pressure Sodium |
1 |
20 watt lamp |
1 |
MAG |
Mag. Transformer |
24 |
|
High Pressure Sodium |
1 |
25 watt lamp |
1 |
MAG |
Mag. Transformer |
29 |
|
High Pressure Sodium |
1 |
35 watt lamp |
1 |
MAG |
Mag. Transformer |
39 |
|
High Pressure Sodium |
1 |
37 watt lamp |
1 |
MAG |
Mag. Transformer |
42 |
|
High Pressure Sodium |
1 |
42 watt lamp |
1 |
MAG |
Mag. Transformer |
46 |
|
High Pressure Sodium |
1 |
50 watt lamp |
1 |
MAG |
Mag. Transformer |
55 |
|
High Pressure Sodium |
1 |
65 watt lamp |
1 |
MAG |
Mag. Transformer |
70 |
|
High Pressure Sodium |
1 |
71 watt lamp |
1 |
MAG |
Mag. Transformer |
76 |
|
High Pressure Sodium |
1 |
75 watt lamp |
1 |
MAG |
Mag. Transformer |
81 |
|