EXCEPTION 1 to Section 130.5(a): Service or feeder for which the utility company provides a metering system that indicates instantaneous kW demand and kWh for a utility-defined period.
EXCEPTION 2 to Section 130.5(a): Electrical power distribution systems subject to California Electrical Code Article 517.
EXCEPTION 1 to Section 130.5(b): For each separate load type, up to 10 percent of the connected load may be of any type.
EXCEPTION 2 to Section 130.5(b): Electrical power distribution systems subject to California Electrical Code Article 517.
Metering Functionality | Electrical Services rated 50 kVA or less | Electrical Services rated more than 50kVA and less than or equal to 250 kVA | Electrical Services rated more than 250 kVA and less than or equal to 1000kVA | Electrical Services rated more than 1000kVA |
Instantaneous (at the time) kW demand | Required | Required | Required | Required |
Historical peak demand (kW) | Not required | Not required | Required | Required |
Tracking kWh for a user-definable period. | Required | Required | Required | Required |
kWh per rate period | Not required | Not required | Not required | Required |
Electrical Load Type | Electrical Services rated 50 kVA or less | Electrical Services rated more than 50kVA and less than or equal to 250 kVA | Electrical Services rated more than 250 kVA and less than or equal to 1000kVA | Electrical Services rated more than 1000kVA |
Lighting including exit and egress lighting and exterior lighting | Not required | All lighting in aggregate | All lighting disaggregated by floor, type or area | All lighting disaggregated by floor, type or area |
HVAC systems and components including chillers, fans, heaters, furnaces, package units, cooling towers, and circulation pumps associated with HVAC | Not required | All HVAC in aggregate | All HVAC in aggregate and each HVAC load rated at least 50 kVA | All HVAC in aggregate and each HVAC load rated at least 50kVA |
Domestic and service water system pumps and related systems and components | Not required | All loads in aggregate | All loads in aggregate | All loads in aggregate |
Plug load including appliances rated less than 25 kVA | Not required | All plug load in aggregate Groups of plug loads exceeding 25 kVA connected load in an area less than 5000 sf | All plug load separated by floor, type or area Groups of plug loads exceeding 25 kVA connected load in an area less than 5000 sf | All plug load separated by floor, type or area All groups of plug loads exceeding 25 kVA connected load in an area less than 5000 sf |
Elevators, escalators, moving walks, and transit systems | Not required | All loads in aggregate | All loads in aggregate | All loads in aggregate |
Other individual non-HVAC loads or appliances rated 25kVA or greater | Not required | All loads in aggregate | All loads in aggregate | All loads in aggregate |
Industrial and commercial load centers 25 kVA or greater including theatrical lighting installations and commercial kitchens | Not required | All loads in aggregate | All loads in aggregate | All loads in aggregate |
Renewable power source (net or total) | Each group | Each group | Each group | Each group |
Loads associated with renewable power source | Not required | All loads in aggregate | All loads in aggregate | All loads in aggregate |
Charging stations for electric vehicles | All loads in aggregate | All loads in aggregate | All loads in aggregate | All loads in aggregate |