EXCEPTION to Section 110.8(d)1: Where the accessible space in the attic is not large enough to accommodate the required R-value, the entire accessible space shall be filled with insulation provided such installation does not violate Section 1202.2 of Title 24, Part 2 or Section 806 of Title 24, Part 2.5.
Insulation Location | Insulation Orientation | Installation Requirements | Climate Zone | Insulation R-Value |
Outside edge of heated slab, either inside or outside the foundation wall | Vertical | From the level of the top of the slab, down 16 inches or to the frost line, whichever is greater. Insulation may stop at the top of the footing where this is less than the required depth. For below grade slabs, vertical insulation shall be extended from the top of the foundation wall to the bottom of the foundation (or the top of the footing) or to the frost line, whichever is greater. | 1 – 15 | 5 |
16 | 10 | |||
Between heated slab and outside foundation wall | Vertical and Horizontal | Vertical insulation from top of slab at inside edge of outside wall down to the top of the horizontal insulation. Horizontal insulation from the outside edge of the vertical insulation extending 4 feet toward the center of the slab in a direction normal to the outside of the building in plan view. | 1 – 15 | 5 |
16 | 10 vertical and 7 horizontal |
Product Type | CRRC Product Category | β |
Field-Applied Coating | Field-Applied Coating | 0.65 |
Other | Not A Field-Applied Coating | 0.70 |
EXCEPTION 1 to Section 110.8(i)4B: Aluminum-pigmented asphalt roof coatings shall meet the requirements of ASTM D2824 and be installed as specified by ASTM D3805.
EXCEPTION 2 to Section 110.8(i)4B: Cement-based roof coatings shall contain a minimum of 20 percent cement and shall meet the requirements of ASTM C1583, ASTM D822, and ASTM D5870.
Physical Property | ASTM Test Procedure | Requirement |
Initial percent elongation (break) | D2370 | Minimum 200% @ 73° F (23° C) |
Initial percent elongation (break)OR Initial Flexibility | D2370 D522, Test B | Minimum 60% @ 0° F (-18° C) Minimum pass 1” mandrel @ 0° F (-18° C) |
Initial tensile strength (maximum stress) | D2370 | Minimum 100 psi (1.38 Mpa ) @ 73° F (23° C) |
Initial tensile strength (maximum stress) OR Initial Flexibility | D2370 D522, Test B | Minimum 200 psi (2.76 Mpa ) @ 0° F (-18° C) Minimum pass 1” mandrel @ 0 ° F (-18 ° C) |
Final percent elongation (break) after accelerated weathering 1000 h | D2370 | Minimum 100% @ 73 ° F (23 ° C) |
Final percent elongation (break) after accelerated weathering 1000 h OR Flexibility after accelerated weathering 1000 h | D2370 D522, Test B | Minimum 40% @ 0 ° F (-18 ° C) Minimum pass 1” mandrel @ 0 ° F (-18 ° C) |
Permeance | D1653 | Maximum 50 perms |
Accelerated weathering 1000 h | D4798 | No cracking or checking 1 |
1. Any cracking or checking visible to the eye fails the test procedure. |